Troubleshooting

12-15

12037
Open Circuit

CP, Flashing

red

Soft

The fast flux up current is less
than 50% of commanded.

Make sure the motor is properly connected.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a fault,
change bit 5 in Fault Select 1 (parameter 20) to 0.

12064
RidethruTime

CP, Solid

green

Warning

There was a drop of 150V and
power did not return within 2
seconds.

Check the incoming power and fuses.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a
warning, change bit 0 in Warning Select 1
(parameter 21) to 0.

12065
Prechrg Time

CP, Solid

green

Warning

The precharge function could not
complete within 30 seconds.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a
warning, change bit 1 in Warning Select 1
(parameter 21) to 0.

12066
Bus Drop

CP, Solid

green

Warning

The bus voltage dropped 150V
below the bus tracker voltage.

Monitor the incoming AC line for low voltage or line
power interruption.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a
warning, change bit 2 in Warning Select 1
(parameter 21) to 0.

12067
Bus Undervlt

CP, Solid

green

Warning

The DC bus voltage fell below the
minimum value (388V DC at
460V AC input).

Monitor the incoming AC line for low voltage or line
power interruption.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a
warning, change bit 3 in Warning Select 1
(parameter 21) to 0.

12068
Bus Cycle>5

CP, Solid

green

Warning

At least 5 ridethrough cycles
have occurred within a 20 second
period. This indicates a converter
problem or a problem with the
incoming power.

Monitor the incoming AC line for low voltage or line
power interruption.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a
warning, change bit 4 in Warning Select 1
(parameter 21) to 0.

12069
Open Circuit

CP, Solid

green

Warning

The fast flux up current is less
than 50% of commanded.

Make sure the motor is properly connected.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a
warning, change bit 5 in Warning Select 1
(parameter 21) to 0.

13000
HW Malfunction

CP, Solid red

Hard

A hardware malfunction
occurred.

Recycle the power. If the fault does not clear, replace the
board.

13001
HW Malfunction

CP, Solid red

Hard

A hardware malfunction
occurred.

Recycle the power. If the fault does not clear, replace the
board.

13002
HW Malfunction

CP, Solid red

Hard

A hardware malfunction
occurred.

Recycle the power. If the fault does not clear, replace the
board.

13003
HW Malfunction

CP, Solid red

Hard

A hardware malfunction
occurred.

Recycle the power. If the fault does not clear, replace the
board.

13004
HW Malfunction

CP, Solid red

Hard

A hardware malfunction
occurred.

Recycle the power. If the fault does not clear, replace the
board.

Fault Code

and Text

LED

Information

Fault

Type

Description

Suggested Action