Parameters

11-67

210

Function In7

1

Use Function In7 to provide input to the function block that is
provided with the 1336 IMPACT drive.

For the timer delay function block, Function In7 specifies the
value to pass to Function Output 1 (parameter 213) when the
timer delay evaluation is false.

For the state machine function block Function In7 is used for the
output if the evaluation of Function In2 (parameter 201) is true
and the evaluation of Function In1 (parameter 198) and the timer
function are false.

For the scale function, Function In7 is the lower word of the value
that you want to use as either the minimum or maximum value for
the output. The upper word of this value is specified in Function
In6
(parameter 209).

For the counter function, Function In7 is used for the Cnt Clr
value. By default, the value is 0. This value can be changed by
the user.

1 Function In7 was added in Version 2.xx.

Parameter number

210

File:group

Application:Prog Function

Parameter type

linkable destination

Conversion

1 = 1

If Function Sel (parameter 212) is 0 – 10, 12, then:
Display

bits

Factory default

00000000.00000000

Minimum value

00000000.00000000

Maximum value

11111111.11111111

If Function Sel (parameter 212) is 11
Display

±x

Factory default

0

Minimum value

-32767

Maximum value

+32767

If Function Sel (parameter 212) is 13, then:
Display

±x

Factory default

0

Minimum value

0

Maximum value

65535

Refer to Chapter 10, Using the Function Block, for more
information.

211

Function In8

1

Use Function In8 to provide input to the function block that is
provided with the 1336 IMPACT drive.

For the state machine function block, Function In8 is used for the
output if the evaluation of Function In2 (parameter 201) is true
and the evaluation of Function In1 (parameter 198) and the timer
on function are true.

1 Function In8 was added in Version 2.xx.

Parameter number

211

File:group

Application:Prog Function

Parameter type

linkable destination

Display

bits

Factory default

00000000.00000000

Minimum value

00000000.00000000

Maximum value

11111111.11111111

Conversion

1 = 1

Refer to Chapter 10, Using the Function Block, for more
information.