Mounting and Wiring Your 1336 IMPACT Drive

2-13

Catalog Number

Base Derate Amps

1

Derate Curve

2,3

Heat Dissipation Drive

Watts

2,3

Heatsink Watts

2

Total Watts

2

B075

120.3

Figure D.14

361

1708

2069

B100

149.2

Figure D.15

426

1944

2370

B125

180.4

Figure D.16

522

2664

3186

BX150

180.4

Figure D.16

606

2769

3375

B150

240.0

Figure D.9

606

2769

3375

B200

291.4

Figure D.10

755

3700

4455

B250

327.4

Figure D.17

902

4100

5002

B300

5

406.4

none

1005

4805

5810

BP300

406.4

Figure D.18

4

4

4

B350

5

459.2

none

1055

5455

6510

BP350

459.2

Figure D.19

4

4

4

B400

5

505.1

none

1295

6175

7470

BP400

481.0

Figure D.20

4

4

4

B450

5

570.2

none

1335

6875

8210

BP450

531.7

Figure D.21

4

4

4

B500

5

599.2

Figure D.22

1395

7800

9200

B600

5

673.4

Figure D.23

1485

8767

10252

B700C

850.0

Figure D.24

1700

9700

5

11400

B800C

983.0

Figure D.24

1900

12000

5

13900

500 – 600V drives

CWF10

2.5

4

25

29

54

CWF20

4.2

4

29

57

86

CWF30

6.0

4

32

87

119

CWF50

7.9

4

35

117

152

CWF75

9.9

none

91

217

308

CWF100

12.0

none

103

251

354

C015

18.9

none

117

360

477

C020

23.6

none

140

467

607

C025

30.0

none

141

492

633

C030

34.6

none

141

526

667

C040

45.1

none

175

678

853

C050

57.2

none

193

899

1092

C060

61.6

4

193

981

1174

C075

85.8

Figure D.25

361

1553

1894

C100

109.1

Figure D.26

426

1978

2504

C125

138.6

Figure D.27

522

2162

2683

C150

159.7

Figure D.28

4

4

4

C200

252.6

Figure D.29

755

3065

3820

C250

283.6

Figure D.30

890

3625

4515

C300

5

298.0

none

926

5015

5941

CX300

300.0

none

926

3990

4930

C350

5

353.6

none

1000

5935

6935

CP350

350.0

Figure D.33

580

6125

6705

CPR 350

350.0

none

580

6125

6705

C400

5

406.4

Figure D.31

1430

7120

8550

CP400

400.0

Figure D.34

711

7000

7711

C450

5

459.2

Figure D.32

1465

8020

9485

C500

5

505.1

Figure D.37

1500

8925

10425

C600

5

599.2

Figure D.38

1610

10767

12377

C650

5

673.4

Figure D.39

1700

12000

14000

C700C

770.0

Figure D.39

1800

9400

6

11200

C800C

800.0

FigureD.39

2000

11300

6

13300

1 Base derate amps are based on nominal voltage (240, 480, or 600V). If the input voltage exceeds the drive rating, the drive output must be

derated. Refer to Figure D.41.

2 Drive ambient temperature rating is 40 degrees C. If ambient exceeds 40 degrees C, derate the drive. Refer to Figures D.1 D.39.

3 Drive rating is based on altitudes of 1000 m (3000 ft) or less. If installed at a higher altitude, derate the drive. Refer to Figure D.40

4 Not available at time of publication

5 IMPORTANT: Two 725 CFM fans are required if an open type drive is mounted in a user supplied enclosure.

6 This is the inverter loss only, common bus configuration 1 kHz PWM.