12-10

Troubleshooting

03010
HW Malfunction

VP, Red 3

blink

Hard

A hardware malfunction was
detected on power up or reset.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Recycle the power. If the fault does not clear, replace the
main control board.

03011
HW Malfunction

VP, Red 4

blink

Hard

A hardware malfunction was
detected on power up or reset.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Recycle the power. If the fault does not clear, replace the
main control board.

03012
HW Malfunction

VP, Red 5

blink

Hard

A hardware malfunction was
detected on power up or reset.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Recycle the power. If the fault does not clear, replace the
main control board.

03014
EE Checksum

VP, Flashing

red

Soft

The parameter database is
corrupt.

Initialize parameters or:

• Perform a Recall Values operation.

• Perform a Save Values operation.

• Verify the parameters.

• Reset the drive.

If the fault still occurs, replace the board.

03015
HW Malfunction

VP, Flashing

red

Soft

A hardware malfunction has
occurred.

Recycle the power. If the fault does not clear, replace the
main control board (B frames through H frames) or the
drive (A frames).

03022
Diff Drv Type

VP, Flashing

red

Soft

The main control board has been
initialized on a different size drive.

Issue a Reset Defaults command to set the drive
parameters back to the default values.

03023
SW Malfunction

VP, Solid red

Hard

A software malfunction has
occurred.

Recycle the power. If the fault does not clear, replace the
main control board. If the fault still occurs, replace the
gate driver board.

03024
SW Malfunction

VP, Solid red

Hard

A software malfunction has
occurred.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Recycle the power. If the fault does not clear, replace the
main control board.

03025
Absolute Overspd

VP, Flashing

red

Soft

The motor speed has exceeded
the speed limit plus Absolute
Overspd
(parameter 24) settings.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

If operating in torque mode, check if the load is allowing
excessive motor speed.

Check if the setting of Absolute Overspd (parameter 24)
or the speed limits (parameters 40 and 41) are too low.

03026
Analog Spply Tol

VP, Flashing

red

Soft

The analog supply tolerance
voltage is outside of the 13V to
18V range.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Possible faulty analog 15V power supply. The power
supply or the main control board may require
replacement.

03029
SW Malfunction

VP, Solid red

Hard

A software malfunction has
occurred.

Recycle the power. If the fault does not clear, replace the
main control board.

03030
SW Malfunction

VP, Solid red

Hard

A software malfunction has
occurred.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Recycle the power. If the fault does not clear, replace the
main control board.

03031
SW Malfunction

VP, Solid red

Hard

A software malfunction has
occurred.

Recycle the power. If the fault does not clear, replace the
main control board.

Fault Code

and Text

LED

Information

Fault

Type

Description

Suggested Action