117 l option in sts, 118 mop increment, 119 mop value – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 236: 120 pulse in ppr, 121 pulse in scale

Advertising
background image

11-38

Parameters

117

L Option In Sts

Use L Option In Sts to view the status of the L Option inputs.

Parameter number

117

File:group

Interface/Comm:Digital Config

Parameter type

source

Display

bits

Factory default

not applicable

Minimum value

00000000.00000000

Maximum value

00000001.11111111

Conversion

1 = 1

Bit

Description

Bit

Description

Bit

Description

Bit

Description

0

TB3-19

3

TB3-23

6

TB3-27

9 – 15 Reserved

1

TB3-20

4

TB3-24

7

TB3-28

Leave 0.

2

TB3-22

5

TB3-26

8

TB3-30 (enable)

118

Mop Increment

Use Mop Increment to set the rate of increase or decrease to the
Manually Operated Potentiometer (MOP) value based on
rpm/second. Mop Increment is only used when the value of
L Option Mode (parameter 116) is 5, 9, 10, or 15.

Parameter number

118

File:group

Interface/Comm:Digital Config

Parameter type

linkable destination

Display

x.x rpm (rpm/second)

Factory default

10% of base motor speed

Minimum value

0.0

Maximum value

base motor speed

Conversion

4096 = base motor speed

Refer to Chapter 9, Applications, for more information.

119

Mop Value

Use Mop Value to view the Manually Operated Potentiometer
(MOP) value. You need to link Mop Value to a reference, such as
Speed Ref 1 (parameter 29) for the drive to follow the Mop
command for speed.

Parameter number

119

File:group

Interface/Comm:Digital Config

Parameter type

source

Display

±x.x rpm

Factory default

not applicable

Minimum value

0.0

Maximum value

base motor speed

Conversion

4096 = base motor speed

Refer to Chapter 9, Applications, for more information.

120

Pulse In PPR

Use Pulse In PPR to set the number of pulses per revolution.

Parameter number

120

File:group

Interface/Comm:Digital Config

Parameter type

destination

Display

x PPR

Factory default

1024

Minimum value

500

Maximum value

20000

Conversion

1 = 1

Refer to Chapter 7, Setting Up the Input/Output, for more
information.

121

Pulse In Scale

Enter the value to use to scale the pulse input. The scale is a
ratio. For example, you would enter 0.5 if you want to scale the
pulse input to half.

Parameter number

121

File:group

Interface/Comm:Digital Config

Parameter type

destination

Display

x.xx

Factory default

1.00

Minimum value

0.01

Maximum value

10.00

Conversion

100 = 1.00

Refer to Chapter 7, Setting Up the Input/Output, for more
information.

Advertising