258 step 4 speed, 259 step 4 value, 260 step 4 type – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 276: 261 step 5 speed, 262 step 5 value, 263 step 5 type

Advertising
background image

11-78

Parameters

258

Step 4 Speed

Parameter 258 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

258

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = Base Motor Speed

259

Step 4 Value

Parameter 259 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 = 1.0 units
TB Input Step: dependent on [L Option Mode Sel]. See P241.

Parameter number

259

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

0=1.0 sec., x TBin, 10 = 1 unit

260

Step 4 Type

Parameter 260 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P258 for time in P259.
2 = TB3 Input Step, operate at speed shown in P258 until this
input goes true.
3 = Encoder Step, operate at speed shown in P258 for units in
P259.

Parameter number

260

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion

261

Step 5 Speed

Parameter 261 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

261

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = Base Motor Speed

262

Step 5 Value

Parameter 262 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 1 = 1 revolution
TB Input Step: dependent on [L Option Mode Sel]. See P241.

Parameter number

262

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

0=1.0 sec., x TBin, 10 = 1 unit

263

Step 5 Type

Parameter 263 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P261 for time in P262.
2 = TB3 Input Step, operate at speed shown in P261 until P262
input goes true.
3 = Encoder Step, operate at speed shown in P261 for units in
P262.

Parameter number

263

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion

Advertising