Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 25

Advertising
background image

Mounting and Wiring Your 1336 IMPACT Drive

2-7

NA = Not Available, use fuses

1

Bulletin 140 - At 480 volts, circuit breaker must have a fuse backup. Refer to the

AB Industrial Control Catalog. At 600 volts, additional restrictions apply. No
limitations in source short circuit ratings.

2

HMCP Circuit Breaker - HMCP Breaker is a magnetic trip device only. Always set

the trip setting as low as possible in a particular application.

3

Current limiting option can extend this value to 200,000A RMS

1336E-B350

298 (400)

NA

NA

NA

-

-

1336E-BP350

261 (350)

NA

NA

HMCP600L6W

E

65,000

1336E-B400

336 (450)

NA

NA

NA

-

-

1336E-BP400

298 (400)

NA

NA

HMCP600L6W

E

65,000

1336E-B450

373 (500)

NA

NA

NA

-

-

1336E-BP450

336 (450)

NA

NA

HMCP600L6W

E

65,000

1336E-B500

448 (600)

NA

NA

NA

-

-

1336E-C001

0.75 (1)

140-MN-0400

100,000

HMCPS003A0

E

65,000

1336E-C003

2.2 (3)

140-MN-0630

100,000

HMCPS007C0

E

65,000

1336E-C007

5.5 (7.5)

140-MN-1000

16,000

HMCPS015E0C

E

65,000

1336E-C010

7.5 (10)

140-MN-1600

6,000

HMCPS015E0C

E

65,000

1336E-C015

11 (15)

140-MN-2000

6,000

HMCPS030H1C

F

65,000

1336E-C020

15 (20)

140-MN-2500

6,000

HMCPS030H1C

H

65,000

1336E-C025

18.5 (25)

140-CMN-4000

65,000

HMCPS050K2C

E

65,000

1336E-C030

22 (30)

140-CMN-4000

65,000

HMCPS050K2C

G

65,000

1336E-C040

30 (40)

140-CMN-6300

50,000

HMCPS050K2C

G

65,000

1336E-C050

37 (50)

140-CMN-6300

50,000

HMCPS100R3C

E

65,000

1336E-C060

45 (60)

140-CMN-6300

50,000

HMCPS100R3C

E

65,000

1336E-C075

56 (75)

140-CMN-9000

25,000

HMCPS100R3C

G

65,000

1336E-C100

75 (100)

KTA3-160S-125

65,000

HMCP150T4C

E

65,000

1336E-C125

93 (125)

KTA3-160S-160

65,000

HMCP150T4C

E

65,000

1336E-C150

112 (150)

KTA3-400S-160

65,000

HMCP150T4C

G

65,000

1336E-C200

149 (200)

KTA-400S-320

65,000

HMCP250J5

I

65,000

1336E-C250

187 (250)

KTA3-400S-320

65,000

HMCP400W5

G

65,000

1336E-CX300

224 (300)

KTA3-400S-320

65,000

HMCP400W5

H

65,000

1336E-C300

224 (300)

KTA3-400S-320

65,000

HMCP400W5

H

65,000

1336E-C350

261 (350)

KTA3-400S-320

65,000

NA

NA

NA

1336E-C400

298 (400)

KTA3-400S-320

65,000

NA

NA

NA

1336E-C450

336 (450)

NA

NA

NA

NA

NA

1336E-C500

373 (500)

NA

NA

NA

NA

NA

1336E-C600

448 (600)

NA

NA

NA

NA

NA

Drive

Catalog Number

Maximum

Rated Vt

kW (HP)

IEC Installations per IEC947-2

UL/CSA Installations

Bulletin 140 Circuit Breaker

HMCP Circuit Breaker

2

Catalog Number

Rated Service Short

Circuit Capability

400/415V

Catalog Number

MCP Trip

Setting

Max. Short

Circuit Amps

3

480V

Advertising