Configuring the scanport controls, Configuring the scanport controls -3 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 127

Advertising
background image

Using the SCANport Capabilities

8-3

Figure 8.2 shows the parameter interactions involved with Logic
Input Sts
.

Figure 8.2
Parameter Interactions

The owner parameters (128 through 132) are covered in the next
section.

Configuring the SCANport
Controls

SCANport has two parts: control and analog I/O. The SCANport
controls are the functions that control the motor, such as start, stop,
and jog. The control can come from up to six SCANport devices,
Logic Cmd Input (parameter 197), and one L Option Board
simultaneously. The control is based on an ownership mechanism that
lets certain functions have only one owner and other functions to have
multiple owners.

Bit 0 — Normal Stop
Bit 1 — Start
Bit 2 — Jog 1
Bit 3 — Clear Fault
Bit 4 — Forward
Bit 5 — Reverse
Bit 6 — Jog 2
Bit 7 — Current Limit Stop
Bit 8 — Coast–to–Stop
Bit 9 — Speed Ramp Disable
Bit 10 — Flux Enable – Magnetizing Flux
Bit 11 — Process Trim Enable
Bit 12 — Speed Ref A
Bit 13 — Speed Ref B
Bit 14 — Speed Ref C
Bit 15 — Reset Drive

C B A
0 0 0 — No Change
0 0 1 — Speed Ref 1
0 1 0 — Speed Ref 2
0 1 1 — Speed Ref 3
1 0 0 — Speed Ref 4
1 0 1 — Speed Ref 5
1 1 0 — Speed Ref 6
1 1 1 — Speed Ref 7

Dir/Ref Owner (Par 128)
Start/Stop Owner (Par 129)
Jog1/Jog2 Owner (Par 130)
Ramp/ClFlt Owner (Par 131)
Flux/Trim Owner (Par 132)

Logic Input Sts (Par 14)

SP Enable Mask (Par 124)

Start/Jog Mask (Par 126)

Clr Flt/Res Mask (Par 127)

Dir/Ref Mask (Par 125)

Dir/Ref Mask (Par 125)

Clr Flt/Res Mask (Par 127)

SCANport 1

SCANport 2

SCANport 3

SCANport 4

SCANport 5

SCANport 6

(Gateway)

L Option Board

Logic Cmd Input

(Par 197)

Bit 0 — Run Ready

Bit 8 — At Set Speed

Bit 1 — Running

Bit 9 — Enable LED

Bit 2 — Command Dir

Bit 10 — Stopped

Bit 3 — Rotating Dir

Bit 11 — Stopping

Bit 4 — Accelerating

Bit 12 — At Zero Spd

Bit 5 — Decelerating

Bit 13 — Speed Ref A

Bit 6 — Warning

Bit 14 — Speed Ref B

Bit 7 — Faulted

Bit 15 — Speed Ref C

C B A
0 0 0 — No Change
0 0 1 — Speed Ref 1
0 1 0 — Speed Ref 2
0 1 1 — Speed Ref 3
1 0 0 — Speed Ref 4
1 0 1 — Speed Ref 5
1 1 0 — Speed Ref 6
1 1 1 — Speed Ref 7

Drive/Inv Status (Par 15)

Control of these functions can

come from only one device:

Any device can control

these functions:

Speed reference

Direction

Local

Start

Jog

Reset drive

Speed ramp disable

Stop

Clear fault

Flux enable

Process trim enable

Advertising