221 fault status 1, 222 fault status 2, 223 warning status 1 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 269

Advertising
background image

Parameters

11-71

221

Fault Status 1

1

Fault Status 1 shows fault conditions that have been configured
to report as drive fault conditions. Each configuration bit matches
the bit definitions of Fault Select 1 (parameter 20) and Fault
Select 2
(parameter 22). When a bit is “1” the condition is true;
otherwise, the condition is false.

1 Fault Status 1 was added in Version 3.xx.

Parameter number

221

File:group

Monitor: Fault Status

Parameter type

source

Display

Bits

Factory default

0000 0000 0000 0000

Minimum value

0000 0000 0000 0000

Maximum value

1111 1111 1111 1111

Conversion

1 = 1

Refer to Chapter 12, Troubleshooting, for more information.

Bit

Condition

0

Ridethru Time

1

Prechrg Time

2

Bus Drop

3

Bus Undervlt

4

Bus Cycles>5

5

Open Circuit

Bit

Condition

6

Reserved

7

Reserved

8

mA Input

9

SP 1 Timeout

10

SP 2 Timeout

11

SP 3 Timeout

Bit

Condition

12

SP 4 Timeout

13

SP 5 Timeout

14

SP 6 Timeout

15

SP Error

222

Fault Status 2

1

Fault Status 2 shows fault conditions that have been configured
to report as drive fault conditions. Each configuration bit matches
the bit definitions of Fault Select 1 (parameter 20) and Fault
Select 2
(parameter 22). When a bit is “1” the condition is true;
otherwise, the condition is false.

1 Fault Status 2 was added in Version 3.xx.

Parameter number

222

File:group

Monitor: Fault Status

Parameter type

source

Display

Bits

Factory default

0000 0000 0000 0000

Minimum value

0000 0000 0000 0000

Maximum value

1111 1111 1111 1111

Conversion

1 = 1

Refer to Chapter 12, Troubleshooting, for more information.

Bit

Condition

0

SpdFdbk Loss

1

InvOvtmp Pnd

2

Reserved

3

MtrOvld Pend

4

MtrOvld Trip

5

Mtr Stall

Bit

Condition

6

Ext Fault In

7

Reserved

8

Reserved

9

Param Limit

10

Math Limit

11

Reserved

Bit

Condition

12

Reserved

13

InOvld Pend

14

Reserved

15

InvOvld Trip

223

Warning Status 1

1

Warning Status 1 shows warning conditions that have been
configured to report as drive warning conditions. Each
configuration bit matches the bit definitions of Warning Select 1
(parameter 21) and Warning Select 2 (parameter 23). When a bit
is “1” the condition is true; otherwise, the condition is false.

1 Warning Status 1 was added in Version 3.xx.

Parameter number

223

File:group

Monitor: Fault Status

Parameter type

source

Display

Bits

Factory default

0000 0000 0000 0000

Minimum value

0000 0000 0000 0000

Maximum value

1111 1111 1111 1111

Conversion

1 = 1

Refer to Chapter 12, Troubleshooting, for more information.

Bit

Condition

0

Ridethru Time

1

Prechrg Time

2

Bus Drop

3

Bus Undervlt

4

Bus Cycles>5

5

Open Circuit

Bit

Condition

6

Reserved

7

Reserved

8

mA Input

9

SP 1 Timeout

10

SP 2 Timeout

11

SP 3 Timeout

Bit

Condition

12

SP 4 Timeout

13

SP 5 Timeout

14

SP 6 Timeout

15

SP Error

Advertising