208 function in5, 209 function in6 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 264

Advertising
background image

11-66

Parameters

208

Function In5

1

Use Function In5 to provide input to the function block that is
provided with the 1336 IMPACT drive.

For the timer delay and state machine function blocks, Function
In5
is used to specify how long after the timer on input is received
before turning on the timer output. When used for these modes,
the timer on signal must be present for as long as you specify in
Function In5.

For the up/down counter function block, Function In5 specifies
how much to subtract from the value when Function In2
(parameter 201) indicates that a rising edge has occurred.

For the scale function block, Function In5 is the lower word of the
value that you want to use as either the minimum or maximum
value for the output. The upper word of this value is specified in
Function In4 (parameter 207).

1 Function In5 was added in Version 2.xx.

Parameter number

208

File:group

Application:Prog Function

Parameter type

linkable destination

Conversion

1 = 1

If Function Sel (parameter 212) is 0 – 8, then:
Display

xxx.xx minutes

Factory default

0.00 minutes

Minimum value

0.00 minutes

Maximum value

655.35 minutes

If Function Sel (parameter 212) is 9 – 13, then:
Display

x

Factory default

0

Minimum value

0

Maximum value

65535

Refer to Chapter 10, Using the Function Block, for more
information.

209

Function In6

1

Use Function In6 to provide input to the function block that is
provided with the the 1336 IMPACT drive.

For the timer delay function block, Function In6 specifies the
value to pass to Function Output 1 (parameter 213) when the
timer delay output is true.

For the state machine function block, Function In6 is used for the
output if the evaluation of Function In2 (parameter 201) is false
and the evaluation of Function In1 (parameter 198) and the timer
on function are true.

For the up/down counter function block, Function In6 specifies
whether the output is a double word (if Function In6 is true) or a
word (if Function In6 is false).

For the scale function block, Function In6 is the upper word of the
value that you want to use as either the minimum or maximum
value for the output. The lower word of this value is specified in
Function In7 (parameter 210).

1 Function In6 was added in Version 2.xx.

Parameter number

209

File:group

Application:Prog Function

Parameter type

linkable destination

Conversion

1 = 1

If Function Sel (parameter 212) is 0 – 10 or 12, then:
Display

bits

Factory default

00000000.00000000

Minimum value

00000000.00000000

Maximum value

11111111.11111111

If Function Sel (parameter 212) is 11, then:
Display

x

Factory default

0

Minimum value

0

Maximum value

65535

If Function Sel (parameter 212) is 13, then:
Display

±x

Factory default

0

Minimum value

-32767

Maximum value

+32767

Refer to Chapter 10, Using the Function Block, for more
information.