This works as shown in figure 10.21 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 187

Advertising
background image

Using the Function Block

10-17

Figure 10.20
Up/Down Counter Function Block

This works as shown in Figure 10.21.

200

Func 1 Eval Sel

2

198

Function In1

199

Func 1 Mask/Val

L Option In Sts

Enter: 00000000.10000000

Up/Down Counter

Function Block

203

Func 2 Eval Sel

0

201

Function In2

202

Func 2 Mask/Val

Enter: 0 This value is not used.

Enter: 0 This value is not used.

212

Function Sel

11

In1 – Count up (rising edge)
In2 – Count down (rising edge)
In3 – Load counter with 0
In4 – Up increment
In5 – Down increment
In6 – 0: Output is a word
In7 – Reserved. Must be 0.

In1

In2

213

Function
Output 1

206

Func 3 Eval Sel

2

204

Function In3

205

Func 3 Mask/Val

Logic Input Sts

Enter: 01110000.00000000

In3

208

Function In5

209

Function In6

Enter: 0

Enter: 0

207

Function In4

Enter: 4096, which is 1000H

Set:

Function In8 (par. 211): 0 rpm

Speed Ref 1 (par. 29): 25 rpm

Speed Ref 2 (par. 31): 50 rpm
Speed Ref 3 (par. 32): 100 rpm

Speed Ref 4 (par. 33): 500 rpm

Speed Ref 5 (par. 34): 250 rpm

Speed Ref 6 (par. 35): 125 rpm

Speed Ref 7 (par. 36): 40 rpm

L Option Mode (par. 116): 8

Dir/Ref Mask (par. 125): 01111111.01111110

197

Logic Cmd

Input

210

Function In7

Enter: 0

In1 is true if

TB3–28 is closed

117

14