background image

Mounting and Wiring Your 1336 IMPACT Drive

2-25

Figure 2.6
Gateway Connection Location

Refer to the documentation that came with your gateway for
installation information.

If you need additional SCANport connections, the 1203-SG2 and
1203-SG4 SCANport expanders are available.

Installing an Interface Board

If you are using an L Option board, refer to Chapter 5, Using the
L Option
, for installation instructions. The terminal blocks used to
connect the L Option board accept wire with the following
specifications:

Connecting the Power to the
Drive

AC Supply Source

1336 IMPACT drives are suitable for use on a circuit that can deliver
up to a maximum of 200,000 rms symmetrical amperes when used
with the AC input line fuses specified in the tables in the
frame-specific chapters.

The 1336 IMPACT drive does not contain input power short circuit
fusing. Specifications for the recommended size and type to provide
drive input power protection against short circuits are on the
following pages.

Connect Your
Communications
Module Here.

Wire information

Description

Minimum wire size

0.06 mm

2

(30 AWG)

Maximum wire size

3.3 mm

2

(12 AWG)

Maximum torque

0.79 N-m (7 lb.-in.)

Wire type

Use only copper wire

Advertising