68 spd/trq mode sel, 69 torque ref 1, 70 slave torque – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 224: 71 min flux level

Advertising
background image

11-26

Parameters

68

Spd/Trq Mode Sel

Use Spd/Trq Mode Sel to select the source for the drive torque
reference. Spd/Trq Mode Sel operates as a selector switch. The
position of the selector determines the torque reference selection
as follows:

Parameter number

68

File:group

Control:Speed/Torq Mode

Parameter type

linkable destination

Display

bits

Factory default

1

Minimum value

0

Maximum value

5

Conversion

1 = 1

For a more detailed description of these bits, refer to the Torque
Reference Overvie
w section in Appendix B, Control Block
Diagrams
.

Value

Description

0

Zero Torque
Zero Torque

1

Speed Reg
Speed Regulate

2

Torque Reg
External Torque

Value

Description

3

Min Trq/Spd
Selects the smallest value when
the torque reference and the
torque generated from the speed
are compared.

4

Max Trq/Spd
Selects the largest value when the
torque reference and the torque
generated from the speed are
compared.

Value

Description

5

Sum Trq/Spd
Selects the sum of the torque
reference and
the torque generated from the
speed.

69

Torque Ref 1

Use Torque Ref 1 to supply an external motor torque reference to
the drive. To select the external torque reference, set Spd/Trq
Mode Sel
(parameter 68) to a value of 2.

Parameter number

69

File:group

Control:Torque Reference

Parameter type

linkable destination

Display

±x.x%

Factory default

+0.0%

Minimum value

-800.0%

Maximum value

+800.0%

Conversion

4096 = 100.0%

70

Slave Torque %

Use Slave Torque % to specify the gain value that is multiplied to
Torque Ref 1 (parameter 69).

Parameter number

70

File:group

Control:Torque Reference

Parameter type

linkable destination

Display

±x.xx%

Factory default

+100.00%

Minimum value

-200.00%

Maximum value

+200.00%

Conversion

4096 = 1.00%

71

Min Flux Level

Use Min Flux Level to set the smallest level of flux used to
convert a torque to a current reference above base speed.
Setting Min Flux Level to a value less than 100%, such as 25%,
will increase the speed regulator gains to compensate for the
loss of gain/bandwidth that occurs above base speed due to field
weakening. Reducing Min Flux Level below 100% may result in
unstable operation above base speed when in encoderless
mode.

Parameter number

71

File:group

none

Parameter type

linkable destination

Display

x.x%

Factory default

100.0%

Minimum value

12.5%

Maximum value

100.0%

Conversion

4096 = 100.0%