Parameters

294

Step 16 Speed

Parameter 294 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

294

File:group

Profile Test Data

Parameter type

Setup

Display

rpm

Factory default

+0.0 rpm

Minimum value

-8 x base sp

Maximum value

+8 x base sp

Conversion

4096 = base motor speed

295

Step 16 Value

Parameter 295 sets the time in seconds for time steps, the
counts in units for encoder steps, and the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)
Encoder Step: 10 =1.0 units
TB Input Step: dependent on [L Option Mode Sel]. See P241

Parameter number

295

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0, 0, 0.0

Minimum value

0.0, 0,0.0

Maximum value

3276.7, 5, 32767.7

Conversion

10=1.0 sec., xTBin, 10 = 1 unit

296

Step 16 Type

Parameter 296 selects the type of step to be used

0 = Not Used (This forces an End Action)
1 = Time Step, operate at speed shown in P294 for time in P295.
2 = TB3 Input Step, operate at speed shown in P294 until this
input goes true.
3 = Encoder Step, operate at speed shown in P294 for units in
P295.

Parameter number

296

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion