B-28

Control Block Diagrams

Drive Fault Detection Overview, Continued

You can configure how you want some situations reported (drive
fault, warning, or ignored), while other situations are always reported
as faults. For the configurable faults, four parameters are provided:
Fault Select 1 (parameter 20), Warning Select 1 (parameter 21), Fault
Select 2
(parameter 22), and Warning Select 2 (parameter 23). For
information about these parameters, refer to Chapter 12,
Troubleshooting.

This section explains how some of the faults are caused and detected.

41

T

C

24

40

FV

>

Warn

<–20˚C

Or

>100˚C

0.5 Sec

Delay

R

F

Not Drive Stopped

Bound Check

Absolute

Overspd

Fwd Motor

Speed Limit

Code

2028

Fault Code 3025

Filtered

Speed

Feedback

Rev Motor

Speed Limit

Absolute Overspeed

100 msec

Delay

Inverter Temperature Check

Power Transistor

Heat Temperature, ˚C

Fault Code 2049

Inverter Overtemp Pending

0.5 Sec

Delay

Look–up

Table

NTC

Input

Power Transistor

Heatsink Temperature

(NTC)

10

15

Drive/Inv

Status

(13V – 18V)

200 msec

Delay

Analog Supply Tolerance

Scale

15 Volt
Analog
Supply

Fault Code 3026

Non–Configurable Faults

file:

Fault Setup

group:

Fault Config

Advertising