246 units traveled, 247 profile cmd lsw, 248 profile cmd msw – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 274: 249 step 1 speed, 250 step 1 value, 251 step 1 type

Advertising
background image

11-76

Parameters

246

Units Traveled

Parameter 246 is a read only parameter that shows the value
traveled from the “home” position in encoder units.

This parameter may roll over if the profile travels more than 3276
units in one direction.

Parameter number

246

File:group

Profile Command

Parameter type

Setup

Display

x.x units

Factory default

4096

Minimum value

-3276.7

Maximum value

3276.7

Conversion

10 = 1.0 unit

247

Profile CMD LSW

Parameter 247 is the lower word of the 32-bit speed reference.
This must be linked to P28 [Speed Ref 1 Frac].

Parameter number

247

File:group

Profile Command

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = base motor speed

248

Profile CMD MSW

Parameter 248 is the upper word of the 32-bit speed reference.
This must be linked to P29 [Speed Ref 1].

Parameter number

248

File:group

Profile Command

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = base motor speed

249

Step 1 Speed

Parameter 249 sets the rpm value for this step. (Scaling: 4096 =
Base Speed)

Parameter number

249

File:group

Profile Test Data

Parameter type

Setup

Display

+/- x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base speed

Maximum value

+8 x base speed

Conversion

4096 = Base Motor Speed

250

Step 1 Value

Parameter 250 sets the time in seconds for time steps, the
counts in units for encoder steps, or the TB3 input to trigger on
for TB Input steps. Scaling:

Time Step: 10 x desired value (10 = 1.0 sec)

Encoder Step: 10 = 1.0 units

TB Input Step: dependent on [L Option Mode Sel]. See P241.

Parameter number

250

File:group

Profile Test Data

Parameter type

Setup

Display

x.xS, x, x.x units

Factory default

0.0,0, 0.0

Minimum value

0.0,0, 0.0

Maximum value

3276.7, 5, 3276.7

Conversion

0=1.0 sec., x TBin, 10 = 1.0 unit

251

Step 1 Type

Parameter 251 selects the type of step to be used

0 = Not Used (this forces an End Action)

1 = Time Step, operate at speed shown in P249 for time in P250.

2 = TB3 Input Step, operate at speed shown in P249 until P250
input goes true.

3 = Encoder Step, operate at speed shown in P249 for units in
P250.

Parameter number

251

File:group

Profile Test Data

Parameter type

Setup

Display

x

Factory default

0

Minimum value

0

Maximum value

3

Conversion

None