13-4

Understanding the Auto-tuning Procedure

Inverter Dgn1 (parameter 174) is defined as follows:

Bits 14 and 15 are reserved.

Inverter Dgn2 (parameter 175) is defined as follows:

If any hardware fault occurs during the open transistor testing, then
the following occur:

The hardware fault is saved.

A phase-to-phase fault is set.

When this bit

is set (1):

Then:

0

A software fault occurred.

1

No motor is connected, or a bus fuse is open.

2

Phase U and W shorted.

3

Phase U and V shorted.

4

Phase V and W shorted.

5

There are shorted modules.

6

A ground fault occurred.

7

A fault occurred before the short module ran.

8

A hardware overvoltage fault occurred.

9

A hardware desat fault occurred.

10

A hardware ground fault occurred.

11

A hardware phase overcurrent fault occurred.

12

There are open power transistor(s).

13

There are current feedback faults.

When this bit

is set (1):

Then:

0

Transistor U upper shorted.

1

Transistor U lower shorted.

2

Transistor V upper shorted.

3

Transistor V lower shorted.

4

Transistor W upper shorted.

5

Transistor W lower shorted.

6

The current feedback phase U offset is too large.

7

The current feedback phase W offset is too large.

8

Transistor U upper open.

9

Transistor U lower open.

10

Transistor V upper open.

11

Transistor V lower open.

12

Transistor W upper open.

13

Transistor W lower open.

14

Current feedback phase U open.

15

Current feedback phase W open.