122 pulse in offset, 123 pulse in value, 124 sp enable mask – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 237

Advertising
background image

Parameters

11-39

122

Pulse In Offset

Enter the minimum speed the pulse input will go to.

Parameter number

122

File:group

Interface/Comm:Digital Config

Parameter type

destination

Display

±x.x rpm

Factory default

+0.0

Minimum value

-base motor speed

Maximum value

+base motor speed

Conversion

4096 = base motor speed

Refer to Chapter 7, Setting Up the Input/Output, for more
information.

123

Pulse In Value

Use Pulse In Value to view the pulse input value. You need to link
Pulse In Value to a reference parameter.

Parameter number

123

File:group

Interface/Comm:Digital Config

Parameter type

source

Display

±x.x rpm

Factory default

not applicable

Minimum value

0.0

Maximum value

+8 x base motor speed

Conversion

4096 = base motor speed

Refer to Chapter 7, Setting Up the Input/Output, for more
information.

124

SP Enable Mask

Use SP Enable Mask to select which SCANport devices can
control the drive. You can choose between:

0 = Disable control
1 = Enable control

Stop is always active, even if you disable a device.

The bits are defined as follows:

Parameter number

124

File:group

Interface/Comm:SCANport Config

Parameter type

linkable destination

Display

bits

Factory default

11111111

Minimum value

00000000

Maximum value

11111111

Conversion

1 = 1

Refer to Chapter 8, Using the SCANport Capabilities, for more
information.

Bit

Description

0

Enable L Opt
Enable the L Option board.

1

Enable SP 1
Enable SCANport device 1.

2

Enable SP 2
Enable SCANport device 2.

Bit

Description

3

Enable SP 3
Enable SCANport device 3.

4

Enable SP 4
Enable SCANport device 4.

5

Enable SP 5
Enable SCANport device 5.

Bit

Description

6

Enable SP 6
Enable SCANport device 6.

7

Enable P197
Enable Logic Cmd Input
(parameter 197).