11-18

Parameters

28

Speed Ref 1 Frac

Use Speed Ref 1 Frac to supply the fractional part of the external
speed reference 1 when speed reference is selected in Logic
Input Sts
(parameter 14).

Parameter number

28

File:group

none

Parameter type

linkable destination

Display

x

Factory default

0

Minimum value

0

Maximum value

65535

Conversion

1 = 1/2^28 base motor speed

29

Speed Ref 1

Enter the speed reference that the drive should use when speed
reference 1 is selected in Logic Input Sts (parameter 14). Speed
Ref 1
supplies the whole number portion of the speed reference.
You can use Speed Ref 1 Frac (parameter 28) to specify the
fractional portion of the speed reference.

Parameter number

29

File:group

Control:Speed Reference

Parameter type

linkable destination

Display

±x.x rpm

Factory default

0.0 rpm

Minimum value

-8 x base motor speed rpm

Maximum value

+8 x base motor speed rpm

Conversion

4096 = base motor speed

30

Speed Scale 1

Enter the gain multiplier used to scale speed reference 1.

Parameter number

30

File:group

Control:Speed Reference

Parameter type

linkable destination

Display

±x.xxxx

Factory default

+1.0000

Minimum value

-3.9999

Maximum value

+3.9999

Conversion

8192 = 1.0000

31

Speed Ref 2

Enter the speed reference that the drive should use when speed
reference 2 is selected in Logic Input Sts (parameter 14).

Parameter number

31

File:group

Control:Speed Reference

Parameter type

linkable destination

Display

±x.x rpm

Factory default

0.0 rpm

Minimum value

-8 x base motor speed rpm

Maximum value

+8 x base motor speed rpm

Conversion

4096 = base motor speed

32

Speed Ref 3

Enter the speed reference that the drive should use when speed
reference 3 is selected in Logic Input Sts (parameter 14).

Parameter number

32

File:group

Control:Speed Reference

Parameter type

linkable destination

Display

±x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base motor speed rpm

Maximum value

+8 x base motor speed rpm

Conversion

4096 = base motor speed

33

Speed Ref 4

Enter the speed reference that the drive should use when speed
reference 4 is selected in Logic Input Sts (parameter 14).

Parameter number

33

File:group

Control:Speed Reference

Parameter type

linkable destination

Display

±x.x rpm

Factory default

+0.0 rpm

Minimum value

-8 x base motor speed rpm

Maximum value

+8 x base motor speed rpm

Conversion

4096 = base motor speed

Advertising