Cable and wiring recommendations – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 331

Advertising
background image

Specifications

A-5

Cable and Wiring
Recommendations

Example

Spacing relationship between 480V AC incoming power leads and
24V DC logic leads.

480V AC leads are class 2; 24V DC leads are class 6.

For separate steel conduits, the conduits must be 76 mm
(3 inches) apart.

In a cable tray, the two groups of leads are to be 152 mm
(6 inches) apart

Spacing Notes

1. Both outgoing and return current carrying conductors are to be

pulled in the same conduit or laid adjacent in tray.

2. Cables of the following classes can be grouped together.

Class 1: equal to or above 601 volts

Classes 2, 3, and 4 may have their respective circuits pulled in
the same conduit or layered in the same tray.

Classes 5 and 6 may have their respective circuits pulled in
the same conduit or layered in the same tray.

Note: Bundle may not exceed conditions of NEC310.

Minimum Spacing in Inches Between

Classes — Steel Conduit/Tray

Category

Wiring

Class

Signal Definition

Signal Examples

Cable Type

1

2/3/4

5/6

7/8

9/10/11

Spacing

Notes

Power

1

AC power (600V or
greater)

2.3kV 3/Ph AC lines

per NEC & local codes

0

3/9

3/9

3/18

Note 6

1/2/5

2

AC power (less than
600V)

460V 3/Ph AC lines

per NEC & local codes

3/9

0

3/6

3/12

Note 6

1/2/5

3

AC power

AC motor

per NEC & local codes

Control

5

115V AC/DC logic

Relay logic/PLC I/O
motor thermostat

per NEC & local codes

3/9

3/6

0

3/9

Note 6

1/2/5

115V AC power

Power supplies,
instruments

6

24V AC/DC logic

PLC I/O

per NEC & local codes

Signal
(Process)

7

Analog signals, DC
supplies

Reference/feedback
signal, 5 to 24V DC

Shielded cable — Belden
8735, 8737, 8404

3/18

3/12

3/9

0

1/3

2/3/4/5

Digital (low speed)

TTL

8

Digital (high speed)

I/O, encoder,
counter pulse tack

Shielded cable — Belden
9728, 9730

Signal
(Comm)

9

Serial
communications

RS-232, 422 to
terminals and
printers

Shielded cable — Belden
RS-232 — 8735, 8737
RS-422 — 9729, 9730

Note 6

1/3

0

11

Serial
communications
(greater than 20k
baud)

PLC Remote I/O,
PLC Data Highway

Twinaxial Cable —
A – B 1770 CD

Advertising