Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 153

Advertising
background image

Applications

9-13

Figure 9.6
An Example of a Remote 10V Pot Wired to a D Frame Drive

In this example, An In 1 Offset (parameter 97) is set to 0, and An In 1
Scale
(parameter 98) is set to 2. This lets the drive use the full

±4096

internal drive units. A link was also made so that Speed Ref 1
(parameter 28) would receive the value of An In 1 Value
(parameter 96) as its speed reference.

The second example is shown in Figure 9.7. In this example, a
0 – 10V pot is wired to a D frame drive to provide speed control. This
example could also apply to any B – H frame drive.

Figure 9.7
An Example of a Remote 0 – 10V Pot Wired to a D Frame Drive

Remote Pot

TB10

4 5

+10V

-10V

An In 1 Offset

= 0

An In1 Scale

= 2

An In1 Filter

= 0

An In1 Value

= +/-4096

3

2

1

Speed Ref 1

Link

97

98

182

29

96

Remote Pot

(2.5K Minimum)

TB10

4 5

10V

0V

An In 1 Offset

= 0

An In1 Scale

= 2

An In1 Filter

= 0

An In1 Value

= +10 = +4096

-10 = -4096

3

2

1

Torque Ref 1

Link

97

98

182

69

96