Using the Function Block

Figure 10.27
Hysteresis Function Block

The hysteresis function provides a band in which the output value
does not change. For example, if an input value is greater than
Input 4, the output value is Input 2. As the input value decrease, the
output value remains Input 2 until the input value is less than Input 5.
Refer to Figure 10.28.

Figure 10.28
Hysteresis

200

Func 1 Eval Sel

0 – 17

198

Function In1

199

Func 1 Mask/Val

I

V

Hysteresis Function Block

203

Func 2 Eval Sel

0 – 17

201

Function In2

202

Func 2 Mask/Val

I

V

212

Function Sel

In1

In2

206

Func 3 Eval Sel

0 – 17

204

Function In3

205

Func 3 Mask/Val

I

V

In3

207

Function In4

208

Function In5

In4

In5

213

Function
Output 1

If:

Then:

In1 > In4

In2 —> Out 1

In1 < In5

In3 —> Out 1

In5 < In1 < In4

No change

14

Hysteresis

Band

(No Change)

In 3

In 2

In 2

In 4

Output Values

In 2

In 3

In 3

In 5