2-12

Mounting and Wiring Your 1336 IMPACT Drive

Use the information in the following table along with the enclosure
manufacturer’s guidelines for sizing.

Catalog Number

Base Derate Amps

1

Derate Curve

2, 3

Heat Dissipation

Drive Watts

2,3

Heatsink Watts

2

Total Watts

2

200 – 240V drives

AQF05

2.3

Figure D.1

13

15

28

AQF07

3.0

Figure D.1

15

21

36

AQF10

4.5

Figure D.1

17

32

49

AQF15

6.0

Figure D.1

21

42

63

AQF20

8.0

Figure D.1

25

56

81

AQF30

12.0

Figure D.1

33

72

105

AQF50

18.0

Figure D.1

42

116

158

A007

27.2

none

156

486

642

A010

33.7

Figure D.2

200

721

921

A015

48.2

Figure D.3

205

819

1024

A020

64.5

Figure D.4

210

933

1143

A025

78.2

Figure D.5

215

1110

1325

A030

80.0

None

220

1110

1330

A040

120.3

Figure D.6

361

1708

2069

A050

149.2

Figure D.7

426

1944

2370

A060

180.4

Figure D.8

522

2664

3186

A075

240.0

Figure D.9

606

2769

3375

A100

291.4

Figure D.10

755

3700

4455

A125

327.4

Same as B250

902

4100

5002

380 – 480V drives

BRF05

1.2

Figure D.1

12

9

21

BRF07

1.7

Figure D.1

13

15

28

BRF10

2.3

Figure D.1

15

20

35

BRF15

3.0

Figure D.1

16

27

43

BRF20

4.0

Figure D.1

19

36

55

BRF30

6.0

Figure D.1

23

54

77

BRF50

10.4

Figure D.1

29

84

113

BRF75

13.9

Figure D.1

70

230

300

BRF100

24.0

Figure D.1

89

331

420

B015

27.2

Figure D.11

117

486

603

B020

33.7

Figure D.2

140

628

768

B025

41.8

Figure D.12

141

720

861

B030

48.2

Figure D.3

141

820

961

BX040

58.7

Figure D.13

175

933

1108

B040

64.5

Figure D.4

175

933

1108

B050

78.2

Figure D.5

193

1110

1303

BX060

78.2

Figure D.5

193

1110

1303

B060

96.9

4

361

1708

2069

1 Base derate amps are based on nominal voltage (240, 480, or 600V). If the input voltage exceeds the drive rating, the drive output must be

derated. Refer to Figure D.41.

2 Drive ambient temperature rating is 40

°C. If ambient exceeds 40°C, derate the drive. Refer to Figures D.1 D.39.

3 Drive rating is based on altitudes of 1000m (3000ft) or less. If installed at a higher altitude, derate the drive. Refer to Figure D.40.

4 Not available at time of publication.

Advertising