Torque Reference Overview

You can use the following block diagram to view how the drive uses
the torque reference parameters.

Torque
Select

Bus Regulator

Torque

Trim

T

pt

From
Trim Control

Bus

Voltage

PI

Regulator

V

Speed

Feedback

Scale

4096

70

Torque

Ref 1

69

Slave
Torque %

+

PI

Speed

Torque

Torque Selection

MIN

MAX

0

0

1

2

+

3

4

Torque Mode Select

Full Wave

Rectify

76

Regen Power

Limit

75

Motor Power Limit = +800%

1.63

Min

Select

Positive Torque

Power Limit

Neg

Torque Limit

5

From
Speed
PI Regulator

Sum

68

Spd/Trq

Mode Sel

84

DC Bus Voltage

12

Inverter Volts

+

+

+

Limit

Y

Max

Select

W

X

+

+

74

Pos

Torque Limit

164

Autotune

Torque

–1

Vf

1

Vf

1

+

Negative

Torque Power

Limit

13 10

Bus Options

(Brake/Regen)

Power Limits

+/–

–/+

Limit Selection

+

+

Notch
Filter

65

Fdbk Filter Sel

(Notch: when value = 4)

185

186

Notch Filtr Freq

Notch Filtr Q

13

5

Bus/Brake Opts

Bus
High
Limit

13

5

Bus Opts

High Limit

1.70

13

5

TP2 10004

1.63 = 10% high line + 5% Chopper Margin
1.70 = 10% high line + 10% Chopper Margin