Troubleshooting

12016
Overvoltage

CP, Solid red

Hard

The DC bus voltage has
exceeded the maximum value.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Monitor the AC line for high line voltage or transient
conditions.

Increase the deceleration time or install the dynamic
brake option because motor regeneration can also cause
bus overvoltages. Refer to the description of Bus Options
(parameter 13) for additional information about bus
overvoltages.

If you are using flux braking, refer to Chapter 9,
Applications
, for information about flux braking.

12017
Desaturation

CP, Solid red

Hard

There was too much current in
the system.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Run the power structure diagnostics.

Check for a shorted motor or motor wiring.

Replace the drive.

12018
Ground Fault

CP, Solid red

Hard

A current path to earth ground in
excess of drive rated current has
been detected at one or more of
the drive output terminals.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Run the power structure diagnostics.

Check the motor and external wiring to the drive output
terminals for a grounded condition.

Replace the drive.

12019
Overcurrent

CP, Solid red

Hard

There was too much current in
the system.

When this condition occurs, the
drive coasts to a stop regardless
of the selected stop type.

Run the power structure diagnostics.

Check for shorted motor or motor wiring.

Replace drive.

12020

CP, Solid Red

Hard

VP and CP have lost
communication

Cycle Power to Drive

Reset Defaults

Replace Main Control Board

12032
RidethruTime

CP, Flashing

red

Soft

There was a bus voltage drop of
150V and power did not return
within 2 seconds.

Check the incoming power and fuses.

If you do not want this condition to be reported as a fault,
change bit 0 in Fault Select 1 (parameter 20) to 0.

12033
Prechrg Time

CP, Flashing

red

Soft

The precharge function could not
complete within 30 seconds.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a fault,
change bit 1 in Fault Select 1 (parameter 20) to 0.

12034
Bus Drop

CP, Flashing

red

Soft

The bus voltage dropped 150V
below the bus tracker voltage.

Monitor the incoming AC line for low voltage or line
power interruption.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a fault,
change bit 2 in Fault Select 1 (parameter 20) to 0.

12035
Bus Undervlt

CP, Flashing

red

Soft

The DC bus voltage fell below the
minimum value (388V DC at
460V AC input).

Monitor the incoming AC line for low voltage or line
power interruption.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a fault,
change bit 3 in Fault Select 1 (parameter 20) to 0 or
decrease the bus undervoltage setpoint.

12036
Bus Cycle>5

CP, Flashing

red

Soft

At least 5 ridethrough cycles
have occurred within a 20 second
period. This indicates a converter
problem or a problem with the
incoming power.

Monitor the incoming AC line for low voltage or line
power interruption.

Refer to the Understanding Precharge and Ridethrough
Faults
section for more information.

If you do not want this condition to be reported as a fault,
change bit 4 in Fault Select 1 (parameter 20) to 0.

Fault Code

and Text

LED

Information

Fault

Type

Description

Suggested Action