170 vd max, 171 vq max, 172 trans dgn config – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 249: 173 autotune/dgn sel

Advertising
background image

Parameters

11-51

170

Vd Max

Use Vd Max to view the maximum D axis voltage allowed on the
motor. The auto-tune routine calculates the value of Vd Max. You
should not change this value.

Vd is short for flux axis voltage.

Parameter number

170

File:group

none

Parameter type

destination

Display

x.x volts

Factory default

calculated

Minimum value

0.0 volts

Maximum value

468.8 volts

Conversion

16 = 1.0

171

Vq Max

Use Vq Max to view the Q axis voltage at which the motor enters
field weakening. The auto-tune routine calculates the value of Vq
Max
. You should not change this value.

Vq is short for torque axis voltage.

Parameter number

171

File:group

none

Parameter type

destination

Display

x.x volts

Factory default

calculated

Minimum value

0.0 volts

Maximum value

468.8 volts

Conversion

16 = 1.0

172

Trans Dgn Config

Use Trans Dgn Config to disable certain transistor diagnostic
tests.

The bits are defined as follows:

Parameter number

172

File:group

Autotune:Autotune Setup

Parameter type

linkable destination

Display

bits

Factory default

00000000.00000000

Minimum value

00000000.00000000

Maximum value

00001111.11011111

Conversion

1 = 1

Refer to Chapter 13, Understanding the Auto-tuning Procedure,
for more information.

Bit

Disables:

0

Cur Fdbk U
I feedback phase U offset

1

Cur Fdbk W
I feedback phase W offset

2

Short Trans
Shorted transistor tests

3

Ground Fault
Ground fault tests

4

Open Tests
Open device tests

Bit

Disables:

5

Reserved
Leave 0.

6

Trans U Up
Power trans U upper for all tests

7

Trans U Lo
Power trans U lower for all tests

8

Trans V Up
Power trans V upper for all tests

Bit

Disables:

9

Trans V Lo
Power trans V lower for all tests

10

Trans W Up
Power trans W upper for all tests

11

Trans W Lo
Power trans W lower for all tests

12 – 15 Reserved

Leave 0.

173

Autotune/Dgn Sel

Use Autotune/Dgn Sel to select the drive diagnostic and
commissioning test.

The bits are defined as follows:

Parameter number

173

File:group

Autotune:Autotune Setup

Parameter type

linkable destination

Display

bits

Factory default

00000000.00000000

Minimum value

00000000.00000000

Maximum value

00000000.00111111

Conversion

1 = 1

Refer to Chapter 13, Understanding the Auto-tuning Procedure,
for more information.

Bit

Selects:

0

Trans Diag
Inverter transistor
diagnostics

1

Mtr Phas Rot
Motor phase rotation
test

Bit

Selects:

2

Lo Measure
Leakage inductance
test

3

Rs Measure
Stator resistance tests

Bit

Selects:

4

Id Measure
Flux current measure

5

Inertia
Inertia tests

Bit

Selects:

6 – 15

Reserved
Leave 0.