Specifications

A-3

Performance

Speed regulation with an encoder

To 0.001% of rated motor speed over a 100:1 speed range

To 0.02 % of rated motor speed over a 1000:1 speed range

Speed regulation without an encoder

±0.5% of rated motor speed over a 120:1 speed range

Torque regulation

To

±5% of rated motor torque, encoderless; ±2% with an encoder.

Power loss ridethrough capability

2 seconds

Flying start

Can start into a spinning motor

Inverter overload capability

Constant torque: 150% of rated drive output for 1 minute.

Motor overload capability

Adjustable to up to 400% of motor rating for 1 minute.

Programmable accel/decel rates

From 0 to 6553 seconds

Current limit

Programmable to 400% of rated motor current, not to exceed 150% of the drive output limit.

Control

Force Technologies: Field-oriented control,
current-regulated, sine code PWM with
programmable carrier frequency

HP

Drive Rating

Carrier Frequency

1 – 3

4 kHz

1 – 12 kHz

7.5 – 30

4 kHz

1 – 12 kHz

40 – 60

4 kHz

1 – 12 kHz

75 – 125

2 kHz

1 – 6 kHz

150 – 250

2 kHz

1 – 6 kHz

300 – 500

2 kHz

1 – 4 kHz

600 – 650

1.5 kHz

1 – 4 kHz

700 – 800

1 kHz

1 – 4 kHz

Refer to the derating guidelines in Appendix D, Derating Guidelines.

Output voltage range

0 to rated voltage

Output frequency range

0 to 250 Hz

Encoder

Incremental, dual channel; isolated with differential transmitter, 100 kHz maximum,
quadrature: 90

°±27° @ 25°C.

Supply power: 12 volts, 500mA
Input: 5 volts (2.5 volts minimum, 10mA minimum)

or 12 volts (9.5 volts minimum, 10mA minimum)

Accel/decel

Independently programmable acceleration and deceleration times. Program from 0 to 6553
seconds in 0.1 second increments.

Current limit

±400% rated motor current up to inverter rating

Inverse time overload capability

Class 20 protection with speed-sensitive response adjustable from 0 – 200% of rated output
current in three speed ranges — 2:1, 4:1, and 10:1. UL certified — Meets NEC article 430.

Input/Output

0 to

±10V DC input

Input impedance of 20K Ohms

4 – 20 mA input

Input impedance of 130 Ohms

Pulse input

Differential, input 5 or 12V, maximum frequency of 100 kHz, 10 mA minimum

0 to

±10V DC output

Output impedance of 100 Ohms, 10 mA maximum

4 – 20 mA output

Output impedance of 273 Ohms; can drive up to 3 inputs

DC power supply

±10V DC, 50 mA per voltage

Fault contact

Resistive rating = 115 VAC/30VDC, 5.0A
Inductive rating = 115 VAC/30VDC 2.0A

Alarm contact

Resistive rating = 115VAC/30VDC, 5.0A
Inductive rating = 115VAC/30VDC, 2.0A