Fset parameters. figure 7.6 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 121

Advertising
background image

Setting Up the Input/Output

7-9

Figure 7.6
Example of Scaling and Offset for 4 – 20 mA Inputs

In this example, the 4 – 20 mA input is offset and scaled to provide
±2048 range from the 4 – 20 mA input. To do this, you would need to:
1. Compare the range of the output that you want to 4 – 20.

In the example shown in Figure 7.6, the ranges were the same, so
we used Step 3.

2. Calculate the offset.

3. Convert the mA range to a digital range, if you have not already

done so. Keep in mind that 20 mA equals 2048 and 4 mA equals
0.

4. Compare the output of the conversion to internal units to the

output range you want.

In the example shown in Figure 7.6, the ranges were different, so
we used Step 5.

5. Calculate the scale. In this example, the internal units were +2048

and you needed 4096; therefore, you would use a scale value of 2.

6. Enter the offset and scale values into the appropriate parameters.

4–20 mA

Input

Offset

Scale

+20

+4

+20

+4

+2048

0

+4096

0

2

0

Analog to

Digital

Converter

20=2048

4=0

Drive Output

Range of the

input after the offset

is applied

Range of the

input in internal

drive units

4 – 20 mA Pot

A

C

B

By subtracting 0mA from
both 20 and 4, you main-
tain the current range,
with +4 as the zero point.

By multiplying +2048 by2,
you get the +4096 range
you were looking for

.

If the ranges are:

Then you:

Go to:

The same (that is, both positive)

Do not need an offset

Step 3

Different

Need an offset

Step 2

If the values are:

Then you:

Go to:

Identical

Do not need to scale the value

Step 6

Different

Need to scale the value

Step 5

Advertising