Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 22

Advertising
background image

2-4

Mounting and Wiring Your 1336 IMPACT Drive

Table 2.B

Maximum Motor Cable Length Restrictions — 500V – 600V Drives

3

All Cable Lengths Given in meters (feet)

.

NR = Not Recommended

Drive

Frame

Drive kW (hp)

Motor kW

(hp)

No External Devices

w/1204-TFB2 Terminator

w/1204-TFA1 Terminator

Reactor at Drive

1

Motor w/Insulation V

P-P

Motor w/Insulation V

P-P

Motor w/Insulation V

P-P

Motor w/Insulation V

P-P

1000V

1200V

1600V

2

1000V

1200V

1600V

2

1000V

1200V

1600V

2

1000V

1200V

1600V

2

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

Any
Cable

A4

0.75 (1)

0.75 (1)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

Not

Recommended

0.37 (0.5)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

1.5 (2)

1.5 (2)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

1.2 (1.5)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

0.75 (1)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

0.37 (0.5)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

2.2 (3)

2.2 (3)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

1.5 (2)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

0.75 (1)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

0.37 (0.5)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

3.7 (5)

3.7 (5)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

2.2 (3)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

1.5 (2)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

0.75 (1)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

0.37 (0.5)

NR

NR

15.2
(50)

NR

182.9
(600)

335.3
(1100)

NR

61.0
(200)

182.9
(600)

B

5.5 – 15
(7.5 – 20)

5.5 – 15
(7.5 – 20)

NR

9.1
(30)

15.2
(50)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

30.5
(100)

91.4
(300)

182.9
(600)

C

18.5 – 45
(25 – 60)

18.5 – 45
(25 – 60)

NR

9.1
(30)

12.2
(40)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

30.5
(100)

91.4
(300)

182.9
(600)

D

56 – 93
(75 – 125)

56 – 93
(75 – 125)

NR

9.1
(30)

33.5
(110)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

61.0
(200)

91.4
(300)

182.9
(600)

E

112 – 224
(150 – X300)

112 – 224
(150 – X300)

NR

9.1
(30)

21.3
(70)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

F

224 – 336
(300 – 450)

224 – 336
(300 – 450)

NR

9.1
(30)

41.1
(135)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

G

224 – 448
(300 – 600)

224 – 448
(300 – 600)

NR

9.1
(30)

41.1
(135)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

H

522 – 597
(700 – 800)

522 – 597
(700 – 800)

NR

9.1
(30)

41.1
(135)

91.4
(300)

182.9
(600)

182.9
(600)

NR

61.0
(200)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

1

A 3% reactor reduces motor and cable stress but may cause a degradation of motor waveform quality. Reactors must have a turn-turn insulation rating of 2100
volts or higher.

2

1329R only

3

Values shown are for nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply
values by 0.85 for high line conditions.

Advertising