Troubleshooting

06042
SP 2 Timeout

VP, Flashing

red

Soft

The SCANport adapter at port 2
has been disconnected and the
logic mask bit for port 2 is set (1).

If the adapter was not intentionally disconnected:

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a fault,
change bit 10 in Fault Select 1 (parameter 20) to 0.

06043
SP 3 Timeout

VP, Flashing

red

Soft

The SCANport adapter at port 3
has been disconnected and the
logic mask bit for port 3 is set (1).

If the adapter was not intentionally disconnected:

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a fault,
change bit 11 in Fault Select 1 (parameter 20) to 0.

06044
SP 4 Timeout

VP, Flashing

red

Soft

The SCANport adapter at port 4
has been disconnected and the
logic mask bit for port 4 is set (1).

If the adapter was not intentionally disconnected:

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a fault,
change bit 12 in Fault Select 1 (parameter 20) to 0.

06045
SP 5 Timeout

VP, Flashing

red

Soft

The SCANport adapter at port 5
has been disconnected and the
logic mask bit for port 5 is set (1).

If the adapter was not intentionally disconnected:

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a fault,
change bit 13 in Fault Select 1 (parameter 20) to 0.

06046
SP 6 Timeout

VP, Flashing

red

Soft

The SCANport adapter at port 6
has been disconnected and the
logic mask bit for port 6 is set (1).

If the adapter was not intentionally disconnected:

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a fault,
change bit 14 in Fault Select 1 (parameter 20) to 0.

06047
SP Error

VP, Flashing

red

Soft

SCANport communications have
been interrupted.

If the adapter was not intentionally disconnected:

• Check the amount of noise on the system.

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a fault,
change bit 15 in Fault Select 1 (parameter 20) to 0.

06073
SP 1 Timeout

VP, Flashing

green

Warning

The SCANport adapter at port 1
has been disconnected and the
logic mask bit for port 1 is set (1).

If the adapter was not intentionally disconnected:

• Check the wiring to the SCANport adapters.

• Replace wiring, SCANport expander, SCANport

adapters, and main control board.

• Complete drive, if required.

If you do not want this condition to be reported as a
warning, change bit 9 in Warning Select 1
(parameter 21) to 0.

Fault Code

and Text

LED

Information

Fault

Type

Description

Suggested Action