229 int torque ref, 230 iq offset, 231 id offset – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 271: 232 function in9, 234 motor voltage

Advertising
background image

Parameters

11-73

229

Int Torque Ref

1

Int Torque Ref shows the value of torque reference that is present
at the output of the torque limiter.

1 Int Torque Ref was added in Version 3.xx.

Parameter number

229

File:group

Monitor: Motor Status

Parameter type

source

Display

±x.x%

Factory default

0.0%

Minimum value

-800%

Maximum value

+800%

Conversion

4096 = Rated Torque

230

Iq Offset

1

IQ Offset contains the LEM U offset required to null the current
error (no motor current flowing). This offset is set automatically
by running the transistor diagnostics.

1 Iq Offset was added in Version 3.xx.

Parameter number

230

File:group

None

Parameter type

linkable destination

Display

±x

Factory default

0

Minimum value

-100

Maximum value

+100

Conversion

1 = 1

231

Id Offset

1

Id Offset contains the LEM W offset required to null the current
error (no motor current flowing). This offset is set automatically
by running the transistor diagnostics.

1 Id Offset was added in Version 3.xx.

Parameter number

231

File:group

None

Parameter type

linkable destination

Display

±x

Factory default

0

Minimum value

-100

Maximum value

+100

Conversion

1 = 1

232

Function In9

1

Use Function In9 to provide input to the function block that is
provided with the 1336 IMPACT drive.

1 Function In9 was added in Version 3.xx.

Parameter number

232

File:group

Application: Prog Function

Parameter type

sink

Display

±x

Factory default

0

Minimum value

-32767

Maximum value

+32767

Conversion

1 = 1

Refer to Chapter 10, Using the Function Block, for more
information.

233

Function In10

1

Use Function In10 to provide input to the function block that is
provided with the 1336 IMPACT drive.

1 Function In10 was added in Version 3.xx.

Parameter number

233

File:group

Application: Prog Function

Parameter type

sink

Display

±x

Factory default

0

Minimum value

-32767

Maximum value

+32767

Conversion

1 = 1

Refer to Chapter 10, Using the Function Block, for more
information.

234

Motor Voltage %

1

Use Motor Voltage % to view the actual line-to-line fundamental
RMS value of motor voltage as a percentage. This data is
averaged and updated every 50 milliseconds.

1 Motor Voltage was added in Version 3.xx.

Parameter number

234

File:group

Monitor:Motor Status

Parameter type

source

Display

x.x%

Factory default

NA

Minimum value

0%

Maximum value

800%

Conversion

4096 = motor volts