IAI America MSCON User Manual

Page 110

Advertising
background image

3.4 Fieldbus

Type

Address Map

102

(ON = Applicable bit is “1”, OFF = Applicable bit is “0”)

Signal Type

Bit

Symbol

Contents

Details

Current

Position

32 bits

32-bit signed integer indicating the current position

Unit: 0.01mm

(Example) If +10.23mm, input 000003FF

H

(1023mm in decimal system).

(Note) Negative numbers are two’s implement.

3.7 (27)

Completed

Position

No.

(Simple

Alarm

Code)

16 bits

PM1 to

PM128

16-bit integer

The positioning complete position number is output

in a binary number once getting into the positioning

band after moving to the target position.

In the case that the position movement has not

been performed at all, or during the movement, “0”

is output. Read it by turning PEND Signal ON after

movement.

The simple alarm code (refer to Chapter 8

Troubleshooting) is output while an alarm is issued

(ALM of Status Signal is ON).

3.7 (27)

b15

EMGS

This signal turns ON during an emergency stop

3.7 (2)

b14

CRDY

This signal turns ON when the controller is

standing by.

3.7 (1)

b13

ZONE2

“ON” for the current position within the zone set

range

The zone range setting is necessary for the

parameter.

b12

ZONE1

“ON” for the current position within the zone set

range

The zone range setting is necessary for the

parameter.

3.7 (11)

b11

PZONE

Position zone

This signal turns ON when the current position is

inside the specified position zone.

3.7 (11)

b10

MODES

Teaching mode signal

(Invalid in Simple Direct Mode)

This signal is ON while the teaching mode is

selected.

3.7 (15)

b9

WEND

Position data import complete

(Invalid in Simple Direct Mode)

This signal turns ON when reading is complete.

3.7 (16)

b8

MEND

This signal turns ON when movement command is

complete, stopping with servo-on and pressing is

missed, and turns OFF when in emergency stop

with servo is OFF and while CSTR Signal is ON

3.7 (21)

b7

BALM

Warning for absolute battery voltage drop

This signal turns ON with battery voltage drop

3.7 (22)

b6

Unavailable

b5

PSFL

This signal turns ON when the actuator missed the

load in push-motion operation.

3.7 (20)

b4

SV

This signal turns ON when operation standby is

complete (Servo is ON).

3.7 (5)

b3

ALM

This signal is ON while an alarm is generated.

3.7 (3)

b2

MOVE

This signal is ON while in movement.

3.7 (8)

b1

HEND

This signal turns ON at home return complete and

is kept unless the home position is lost due to a

fact such as an alarm.

3.7 (6)

P

LC

In

pu

t

Status

Signal

b0

PEND

This signal turns ON when positioning is complete

and stopping with servo-on, and turns OFF when

pressing is missed and while CSTR Signal is ON

3.7 (9)