9

7. For the rotary actuator, it is necessary to pay attention to cable breakage due to

twisting and other factors.

Especially for the type with a through hole in the center of rotation, and when using it with

cables going through the hole, and also for the actuator with 360q rotation, special care is

required because there is no limit to the rotation in one direction.

8. Limitations on operation of rotary actuator in index mode

Rotary actuators of 360q specification can select the normal mode for finite rotations or the

index mode enabling multi-rotation control by using parameter No.79 “Rotational axis mode

selection”.

[Refer to Chapter 7 Parameter.]

The following limitations are applied to the index mode:

1) Index Mode cannot be selected in the absolute type controllers. It will issue Alarm Code

0A1 “Parameter Data Error”.

2) In the JOG operation by PC software, a teaching pendant or PIO Signal, the indicated

range in one time is from 0 to 360.00q and that makes one turn.

3) Pressing is unavailable. The pressing torque can only be set to 0.

4) Do not issue positioning command around 0q repeatedly during movement near 0°. Failure

to follow this may cause the actuator to rotate in the direction reverse to the specified

rotation direction or operate indefinitely.

5) Soft stroke limit is invalid in the index mode.



9. According to sequence program creation

Please note the following things when creating a sequence program.

When data transfer is necessary between two devices that have a different scan time from each

other, duration more than the longer scan time is required to certainly read the signal. (To have

the loading process on PLC side safely, it is recommended to set the timer to at least twice

longer than the long scanning time.)


䧎䎃

Operation Image䎃





















This controller

(scan time 1msec)

PLC (Programmable Logic Controller)

(example: scan time is 20msec)

Output

Process

Input

Process

As shown in the diagram, the input and output

timings of two devices that have different scan

time do not match, of course, when transferring

a signal.

There is no guarantee that PLC would read the

signal as soon as this controller signal turns

ON.

In such a case, make the setting to read the

signal after a certain time that is longer than the

longer scan time to ensure the reading process

to succeed on the PLC side.

It is the same in the case this controller side

reads the signal.

In such a case, it is recommended to ensure 2

to 4 times of the scan time for the timer setting

margin.

It is risky to have the setting below the scan

time since the timer is also processed in the

scan process.

In the diagram, PLC can only read the input

once in 20msec even though this controller

output once in 1msec.

Because PLC only conducts output process

once in 20msec, this controller identifies the

same output status for that while.