IAI America MSCON User Manual

Page 297

Advertising
background image

Chapter 8

Troubleshooting

289

Alarm

Code

Alarm Name

Cause/Treatment

81

Parameter Check

Sum Error

Cause

: There is a possibility that the memory data inside MSCON has

destroyed.

Treatment : Establish all the settings again on Gateway Parameter Setting

Tool or write the backup data if it exists.

90

Driver Board Mount

Error

Cause

: The number of axes (number of driver boards) set in Gateway

Parameter Setting Tool does not match with the number of the

actually connected axes.

Treatment : Match the numbers of the axes.

9C

Fieldbus Module Not

Detected

Cause

: Communication board for Fieldbus was not detected.

1) Communication board is not inserted.

2) Malfunction of communication board

Treatment : Turn the power OFF and reboot. If the same error occurs

again, please contact IAI.

9E

Fan Error

Cause

: A Fan error was detected.

Treatment : It is considered that it is the end of the product life of the fan

(approximately 3 years). Replace the fan.

A0

Control Power

Overvoltage

Cause

: Control power voltage reached beyond the overvoltage

threshold (120% of 24V DC = 28.8V).

1) The voltage of 24V DC power supply is high.

2) A faulty part inside the controller

Treatment : Check the voltage of the input power supply.

A1

Control Power

Voltage Drop

Cause

: The control power voltage dropped less than the voltage drop

threshold (70% of 24V DC = 16.8V).

1) The voltage of 24V DC power is low

2) A faulty part inside the controller

Treatment : Check the power voltage.

If the voltage is normal, please contact IAI.

A2

Motor Power Voltage

Error

Cause

: 1) There is a lack in number of regenerative resistors.

2) Malfunction of component inside the controller can be

considered.

Treatment: 1) Add some more regenerative resistors.

2) If it occurs often, possibility of controller malfunction is high.

Please contact IAI.

AB

Assumed

Regenerative

Discharge Excessive

Power

Cause

: The regenerative electric power exceeded what can be dealt

with the regenerative resistor.

Treatment : Decrease the acceleration/deceleration speed, revise the

operation interval or connect an external optional regenerative

resistor.

AC

Continuous

Regenerative

Excessive Discharge

Cause

: The regenerative electric power exceeded what can be dealt

with the regenerative resistor.

Treatment : Decrease the acceleration/deceleration speed, revise the

operation interval or connect an external optional regenerative

resistor. If there is no improvement even with the treatment, it

is likely a malfunction of the controller.

FFF Power-on Log

It is the log at the power being on (it is not an error).