Chapter 2 Wiring

58

3) PROFIBUS-DP Type

5 1

9 6

Cable

Shield

Red B line (Positive side)

Use the type A cable for PROFIBUS-DP (EN5017).

Green A line (Negative side)

PROFIBUS-DP

Connector

Model

Remarks

Cable Side

D-sub 9-pin connector (Male)

Please prepare separately

Controller Side D-sub 9-pin connector (Female)

Pin

No.

Signal Name

Contents

Applicable Cable

1

NC

Unconnected

2

NC

Unconnected

3

B-Line

Communications Line B

(RS485)

4

RTS

Request for Sending

5

GND

Signal GND (Insulated)

6

+5V

+5V Output (Insulated)

7

NC

Unconnected

8

A-Line

Communications Line A

(RS485)

9

NC

Unconnected

PROFIBUS-DP

Dedicated Cable

(Note): Connect a terminal resistor (220:) between A-Line and B-Line to

the end of the network. [Refer to 2.2 [8] Field network Circuit (For

Field network Type)]

1

5

6

9

Front view of

connector on

controller side

Advertising