IAI America MSCON User Manual

Page 35

Advertising
background image

Chapter 1 Specifications Check

27

1.3.3 Selection of Leak Current Breaker

• It may be mandatory by law to install a leakage breaker.

• A ground fault circuit interrupter needs to be selected carefully considering the purposes of

prevention of fire and protection of human (Determined by law).

• Leak current varies depending on the capacity of connected motor, cable length and the

surrounding environment. Measure the leak current at the point where a ground fault circuit

interrupter is to be installed when leakage protection is conducted.

• Use the harmonic type (for inverter) for the ground fault circuit interrupter.

1.3.4 Control Power (24V DC) Capacity

Follow the description below for the calculation of 24V DC power capacity.

(1) Control Power Current Consumption :

Select from control power supply current in the table below ·················································· 1)

Number of Controlled

Axes

(Note1)

1 axis

2 axis

3 axis

4 axis

5 axis

6 axis

Control Power Unit

Heating Value [W]

25.5

31.5

38.2

44.2

50.9

56.9

Control Power

Capacity [A]

1.1

1.3

1.6

1.8

2.1

2.4

Note 1: See the line of max. number of controlled axes connectable to corresponding

MSCON.



It can be defined on the manufacturing name plate.

MSCON-C-*-• • • •: “*” is the maximum number of connectable axes.

(2) Current Consumption of Brake Power Supply:

1A or 0.5A

(Note 2)

×

number of brake-equipped actuators························································ 2)

Note 2: The maximum current of 1A per actuator runs for approximately 100ms when a brake

is released. The current consumption after the release is 0.5A per unit.

Calculate the capacity with 0.5A per unit when a 24V DC power supply corresponding

to transient load change such as peak load appliance is used and capable for the

maximum current described above. For other cases, calculate with 1A per unit.

(3) Add the Control Power In Rush Current: 7A ·········································································· 3)

[Selection of Power Supply]

Usually, the rated current is to be approximately 1.3 times higher than the total of Control

Power 1) and Motor Power 2) above considering approximately 30% of margin to the load

current. However, considering the inrush currents [excitation (3)], even though it is a short

time, select a power supply with sufficient “peak load capacity”. If a power supply with

insufficient peak capacity is utilized, a transient voltage drop or cutoff may occur. This may

present issues with power supplies providing remote sensing functionality.

(Remark) Selection of Power Supply Protection Circuit Breaker

It is recommended that the power supply protection is conducted on the primary side (AC

power side) of the 24V DC power supply unit.

If having 24V DC turned ON/OFF, keep the 0V connected and have the +24V ON/OFF

(cut one side only).

Be careful to the in-rush current of the 24V DC power supply unit when making a

selection. (Check it in the operation characteristics curve graph in a catalog provided by

the supplier.)

Consider the current that enables to cutoff the current even when a short circuit current is

flown for the rated cutoff current.

y

Rated Interrupting Current > Short Circuit Current = Circuit Breaker Primary Power

Capacity / Power Voltage

y

(Remark) In-rush Current of IAI Power Supply Unit PS241 = 50 to 60A, 3msec

Advertising