6 control signals for direct indication mode – IAI America MSCON User Manual

Page 111

Advertising
background image

3.4 Fieldbus

Type
Address Map

103

3.4.6 Control Signals for Direct Indication Mode

This is an operation mode to indicate directly with values for the target position, positioning

width, speed, acceleration/deceleration and pressing current.

Set a value to each input and output data register. Set to the parameters when using the zone

signals.

The main functions of MSCON capable to control in this mode are as described in the following

ROBO cylinder function

{

: Direct control

ٌ

: Indirect control

×: Disable

Remarks

Home-return operation

{

Positioning operation

{

Speed and

acceleration/deceleration

setting

{

Pitch feeding (Incremental)

{

Pressing operation

{

Speed change during

movement

{

Operation at different

acceleration and

deceleration

×

Pause

{

Zone signal output

ٌ

Parameters must be set.

PIO pattern selection

×

(1) PLC Address Composition

(m is PLC input and output top word address for each axis number)

PLCĺMSCON (PLC Output)

MSCONĺPLC (PLC Input)

Target Position

m to m+1

Current Position

m to m+1

Positioning Width

m+2 to m+3

Command Current

m+2 to m+3

Command Speed

m+4

Current Speed

m+4

Acceleration/Deceleration

m+5

Unavailable

m+5

Current limitation value

while pressing

m+6

Alarm Code

m+6

Control Signal

m+7

Status Signal

m+7

[Refer to Section 3.4.2 for the address maps for each Fieldbus.]

This mode is not applicable for CompNet and MECHATROLINK specifications.