Control and functions of Input and output signals of Modes other than Remote I/O Mode

Power Supply and Cutof

f

149

(6) Home return (HOME)

PLC Output Signal

Home return completion (HEND) PLC Input Signal
Moving (MOVE)

PLC Input Signal

Positioning complete (PEND)

PLC Input Signal

Operation

Mode

Positioner 1

Simple Direct

Direct numeric

specification

Direct numeric

specification 2

Positioner 2

Positioner 3

{

: Equipped

× : Not equipped

{

{

{

{

{

{

HOME Signal is a signal to conduct an automatic home-return operation.

Once HOME Signal is turned ON, this signal is processed as a rise (ON-edge), and the

actuator starts home-return operation. Once the home-return operation is completed, the

home-return operation complete signal HEND turns ON. The home return complete signal

HEND is kept ON unless the home position is lost. The positioning complete signal PEND turns

OFF and the moving signal MOVE turns ON during a home-return operation.

Home Return Signal

HOME

(PLC → MSCON)

Homing Completion Signal

HEND

(MSCON → PLC)

Positioning Completion Signal

PEND

(MSCON → PLC)

Moving Signal

MOVE

(MSCON → PLC)

Caution: If an actuator of Incremental Type is connected, and in Position * Mode and Simple

Direct Mode, when the positioning command is issued without performing the

home-return operation after the power is turned ON, the positioning can be

performed once only after the automatic home-return operation is executed.

Exercise caution that in the derect indication mode, issuing a positioning command

to a given position following the power ON, without performing a home return first,

will generate an alarm “Error Code 83: ALARM HOME ABS (absolute position move

command when home return is not yet completed)” (operation-reset alarm).