IAI America MSCON User Manual

Page 190

Advertising
background image

3.8 Control and functions of Input and output signals of Remote I/O Mode

182

(2) Infinite Rotation Control

Making the shortcut selection valid and moving the actuator in a specific direction

continuously allows the actuator to be rotated continuously as a motor. The continuous

operation can be done as described below.

[Operation Examples]

This example rotates the actuator by 2 turns and finally stops it at position No.4.

Position No.

Position

1

0

2

120

3

240

4

90

Enter position data assuming 1q =

1mm.

(Example) 1.2 is assumed as 1.2q.

1) Widen the positioning widths of position No.1 to 3 so that they are located before the position

at which deceleration is started.

2) Positioning of position No.1 makes positioning complete signal (PEND) turned ON before

deceleration is started.

If PEND is turned ON, positioning of position No.2 is executed. Similarly, positioning is

repeated in the order of position No.3 o 1 o 2 o 3 o 4. Because the normal positioning

always gives position data specified last the highest priority, the actuator can be rotated

continuously.

3) If the speeds in position No.1 to 4 are set to be the same, the actuator can be rotated at the

same speed. Then the actuator is stopped at the positioning set in position No.4. The

number of rotations is defined by the number of repeats of position No.1 to 3.

Position No.4

Position No.1

Position No.2

Position No.3

Position No.1

(Positioning width)

Position No.2

(Positioning width)

Position No.3

(Positioning width)

Position No.1

(Positioning width)

Position No.2

(Positioning width)

Position No.3

(Positioning width)

Actual operation

Position No.1

Positioning

Position No.2

Positioning

Position No.3

Positioning

Position No.1

Positioning

Position No.2

Positioning

Position No.3

Positioning

Position No.4

Positioning

Advertising