3.8 Control and functions of Input and output signals of Remote I/O Mode

208

 

Caution: (1) At occurrence of an alarm in the release level

Note 1

, RES can reset the

alarm. Cancel the remaining moving distance after confirmation that

alarm signal *ALM (being ON in normal state and OFF at occurrence of

an alarm) is set to ON.

Note 1: [Refer to 8.4 Alarm List for details of alarms.]

(2) Turning *STP OFF with the actuator being in the positioning complete

state causes PEND to be turned OFF. Note that this situation may not

occur when a sequence program is created.

(2) Use of start signal ST*

Stop

status

Start signal

Velocity

Time

Input start

signal for

position 1

(Moving start)

Moving

comp.

Positioning

completion

signal output

Deceleration

2)

3)

1)

4) 5)

ON

OFF

Decelerate and

stop by start signal

input to Position 1

being OFF

Movement

resumed

by start signal

input to Position 1

being ON

Acceleration

Deceleration

Acceleration

2)

3)

1)

4)

5)

„

Control method

If start signal ST* is turned OFF during movement, the actuator can be paused.

Use the control method for interlock in case where an object is invaded into the moving

direction of the actuator being moved.

1) If the ST* signal is turned OFF during movement, the actuator is paused. The deceleration is

the value set in the position table.

2) Turning the ST* signal OFF causes the positioning to be interrupted and deemed complete

signal PEND to be turned ON.

3) If the ST* signal is turned ON again, the remaining movement is continued. The acceleration

is the value set in the position table.

Before

operation

Positioning

complete state

Operation

Temp.

stop

Cont.

Op.

Position

complete

Start Signal

ST*

(PLCoMSCON)

Positioning Completion Signal

PEND

(MSCONoPLC)

Operation of actuator

PEND turned

ON

PE* not

turned ON

Current Position No.

PE*

(MSCONoPLC)