Chapter 8

Troubleshooting

296

Alarm

Code

Alarm

Level

Alarm Name

Cause/Treatment

0C0

Actual speed excessive

Cause

: This indicates the number of motor rotation

exceeded the number of allowable rotation.

1) The slide resistance of the actuator is locally

high.

2) The load is increased too much due to a external

force.

With the reasons above, it can be considered a

sudden speed increase has occurred before

detecting the servo error.

Treatment : Even though this would not occur in normal

operation, check if there is any abnormality in the

parts assembly condition. Also check if there is a

possibility that an external force may be applied in

the direction of the actuator movement.

0C2

Operation

release

Overrun sensor

detected

Cause

: This indicates that a signal from the OT sensor

(option) installed at the mechanical end is detected.

1) The actuator was moved by hand or by external

force being applied while the servo was OFF

(normal detection).

2) The actuator was jogged or operated by

pulse-train in a condition where the home

coordinates were not yet established and thus

the soft stroke limit did not function correctly

(normal detection).

3) The home position achieved is not correct, or in

the case of an absolute type controller the

coordinates have shifted due to an inappropriate

absolute reset position.

4) There is a mismatch between the sensor

characteristics and the setting in Parameter

No.19 “Overrun sensor input polarity”, or the

wiring layout is wrong.

5) There is a mistake in the mating of the controller

and actuator, or the settings in Parameters No.3

and 4 “Soft limit value” and Parameter No.77

“Ball screw limit length” are not appropriate.

Treatment : If 1) or 2) is suspected, move the actuator in the

opposite direction by hand.

If this error occurred inside the effective stroke

range, 3), 4), or 5) is a likely cause.

For 3), conduct a home-return operation to check

the home position. Conduct the absolute reset

again if it is the absolute type. Contact us if the

home position would not come to the proper

position.

If 4) or 5) are suspected, please contact IAI.

0C4

Cold start

Exceeded allowable

time of exceeding torque

allowing continuous

pressing

Cause

: The continuous pressing time exceeds the time set

for parameter No.89 “Allowable time of exceeding

torque allowing continuous pressing”.

Treatment : Check the sequence again.

Set the pressing time to be within the setting time.