Chapter 8

Troubleshooting

298

Alarm

Code

Alarm

Level

Alarm Name

Cause/Treatment

0D8

Deviation overflow

Cause

: This alarm indicates that the position deviation

counter has overflowed.

1) The speed dropped or the actuator stopped due

to the effect of external force or overload.

2) The excited-phase detection operation following

the power-on is unstable.

3) The power supply voltage dropped.

4) Servo gain number is too small

Treatment : 1) This error occurs when the actuator cannot be

operated as it is commanded. Check the load

conditions such as if the work is touching to the

surrounding object, or brake is properly

released, and remove the cause.

2) Overload can be concerned. Revise the

transportable weight and redo the home-return

operation.

3) Check for the source voltage.

0D9

Software stroke limit

exceeded

Cause

: The current position of the actuator exceeds the

software stroke limit.

Treatment : Return the actuator to be within the range of the

software stroke limit.

0DC

Operation

release

Pressing motion range

over error

Cause

: 1) After the pressing operation has complete, the

force to push back is too large and the pushed

back to the pressing start position (“Position” in

the position table).

2) The actuator touched the work during the

approach movement before the pressing

movement.

Treatment : 1) Revise the setting and adjust it so the force to

push back gets smaller.

2) Set the “Position” setting in front in the position

table to shorten the approach distance.

0E0

Cold start

Overload

Cause

: 1) The work weight exceeds the rated weight, or an

external force is applied and the load increased.

2) If the actuator is equipped with a brake, the

brake is not released.

3) The slide resistance of the actuator is locally

high.

Treatment : 1) Check the work and its surrounding area to

remove the cause.

2) Turn ON the brake release switch to see if the

brake is released.

If the brake is not released, the brake itself may

be faulty, cable may be disconnected, or the

controller may be faulty. Please contact IAI.

3) In the case that the work can be moved by hand,

move it. Then, check that there is no location

where a sliding resistant is too large.

Check if the installation face is distorted. When

the error occurs in operation of the actuator only,

Please contact IAI.

Caution

Restart the operation after making sure to remove the cause.

If you cannot determine that the cause is removed

completely, wait for at least 30 minutes before turning on the

power to prevent the motor coil from burning.

Generating this error repeatedly without waiting long enough

could burn down the motor coil.