Chapter 7 Parameter

264

[26] Auto servo motor OFF delay time 1, 2, 3 (Parameter No.36, No.37, No.38)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

36 Auto Servo-motor OFF Delay

Time 1

ASO1

sec

0 to 9999

0

37 Auto Servo-motor OFF Delay

Time 2

ASO2

sec

0 to 9999

0

38 Auto Servo-motor OFF Delay

Time 3

ASO3

sec

0 to 9999

0

Set the duration before the servo turns OFF after positioning process is complete when the

power saving function is used.

[Refer to Chapter 5 Power-saving Function.]


[27] Position complete signal output method (Parameter No.39)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

39 Position Complete Signal Output

Method

FPIO

-

0: PEND

1: INP

0

This is the parameter to select the type of the positioning complete signals to be used.

It is available except for when PIO Pattern = 5 (Solenoid Valve Type 2 [3-point type]) is

selected.

There are 2 types of positioning complete signals and the output condition would differ

depending on whether the servo is ON after the positioning is complete or the servo is OFF.

Setting

Signal Type

During Servo ON

(positioning complete)

During Servo OFF

0

PEND

It will not turn OFF even if the

current position is out of the range

of the positioning width.

Turns OFF in any

case

1

INP

Turns ON when the current position is in the positioning

width, and OFF when out of it.

Complete position No. outputs PM1 to PM** and current position No. outputs PE0 to PE6 are

issued in the similar way.

[28] Home return input disable (Parameter No.40)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

40 Home-return Input Disable

FPIO

-

0: Enabled

1: Disable

0

This parameter defines whether the home return input signal is disabled or enabled.

Normally this parameter need not be changed.

Set Value

Description

0

Enabled (Use)

1

Disable (Does not use)