Chapter 4 Configuring the Ultra5000 Drive

The following command can be executed for a Motor window of an online
Ultra5000 drive.

Thermal

Integral Thermostat

Indicates whether the motor has a built-in thermostat. Settings
are: Yes or No.

Software Protection

Indicates whether the motor thermal protection software is
activated. Settings are: Yes or No.

Rth(w-e)

Thermal resistance from the winding to the encoder, in degrees
centigrade/watt (°C/Watt).
Note: This setting applies and is visible only if Software
Protection is set to Yes.

Cth(w-e)

Thermal capacitance from the winding to the encoder, in Watt-
seconds per degree centigrade (Watt-second/°C).
Note: This setting applies and is visible only if Software
Protection is set to Yes.

Rth(w-a)

Thermal resistance from the winding to ambient, in degrees
centigrade/watt (°C/Watt).
Note: This setting applies and is visible only if Software
Protection is set to Yes.

Cth(w-a)

Thermal capacitance from the winding to ambient, in Watt-
seconds per degree centigrade (Watt-second/°C).
Note: This setting applies and is visible only if Software
Protection is set to Yes.

Command

Description

Refresh Data

Reads the motor definition information from the motor database
and reapplies it to the drive.
Note: This command is useful when a motor definition in the
motor database has been changed.

Status

Description