Configuring the Kinetix 3 Drive Chapter 5

The Faults window has these commands.

Customize the Faults window for your Kinetix 3 drive by selecting one or more of
these commands:

Click Show Status to display or hide the Status pane.

Click Show Commands to display or hide the Commands pane.

Click Setup to open the window, where you can customize the status
display for this window.

Click Revert to return parameter settings to the values they held when you
opened this window.

E.108 E.CdFrE Position

Command

Frequency Error

Input frequency limit
exceeded

Verify hardware type

selected in the drive
matches the physical
hardware.

Change from open

collector to line drive.

Reduce the speed

command.

Apply gearing.

E.112 E.EStoP

Emergency Stop

Emergency stop (E-STOP)
signal detected

Remove Emergency

stop conditions.

Clear E-STOP.

E.11e E.IrAnG

Indexing Position Range
Overflow

The value of a Position
Parameter for indexing is
out of the range.

Use a value within the
range of -2,147,483,647
…2,147,483,647

E.114 E.ouCUr Motor

Phase

Over

Current

Problem with control or
main power circuitry if
this error occurs when
power is turned on.

Check wiring and power.

Excessive current to the
motor if this error occurs
during operation (current
more than 300% of the
rated current to the
motor more than 10 ms).

Check power, and set or
adjust the acceleration
and deceleration times.

Command Description

Fault History

Opens the Fault History window, where you can view a list of the
last 20 fault events that occurred since the drive was powered-up.

Clear Faults

Clears all drive faults.

Fault Detail

Opens the Fault Detail window.

Save Parameters

Saves the current working values as power-up values in memory
for the selected online drive and all of its children.

Status Description Possible Cause

Suggested Action