Rockwell Automation Publication 2098-UM001G-EN-P - February 2011

291

Configuring the Kinetix 3 Drive Chapter 5

E.009 E.UdutG

Bus Undervoltage

Low AC line/AC power
input

Verify voltage level of

the incoming AC
power.

Check AC power

sources for glitches or
line drop.

Install uninterruptible

power supply (UPS) on
the AC input.

Attempted to enable
drive without main
power active.

Verify input is within
specification.

E.010 E.ouutG

Bus Overvoltage

Excessive regeneration
of power (When the
motor is driven by an
external mechanical
force, it may regenerate
too much peak energy
through the drive’s power
supply and the drive
faults to save itself from
an overload.)

Verify shunt circuit.

Adjust motion profile

to stay within the
range of the
regenerative resistor.

Replace regenerative

transistor.

Replace drive.

Excessive AC input
voltage

Verify input is within
specification.

E.012 E.HFAIL

Home Search Failed Homing

is

not complete

until the time defined in
Homing time limit (IN-
01.11) is elapsed.

Increase the time

defined in Homing
time limit (in-01.11).

Set a value other than

'0' in Homing Velocity
(In-01.02) and Creep
Velocity (IN-01.03).

Check if there is any

obstacle that disturbs
Homing.

Check mechanical

parts and parameter
settings for Homing.

E.018 E.ouSPd

Motor Overspeed

Motor speed exceeds
maximum

Confirm encoder

wiring.

Retune the drive

system.

Verify the input gain

of external speed or
torque commands.

E.019 E.PoSEr

Excess Position Error

Position error exceeds
permitted value.

Increase following

error limit.

Check position loop

tuning.

Status Description Possible Cause

Suggested Action