Configuring the Ultra5000 Drive Chapter 4

26: User Velocity

ON indicates the User
Velocity Fault level,
above, has been
exceeded.

User-specified velocity
level exceeded.

Increase User Velocity

Fault Level and Time
to a less restrictive
setting.

29: Excess
Output Frequency

ON indicates the motor
encoder output
frequency exceeds the
maximum value.
Note: This fault can be
generated only when the
encoder output is
synthesized by the
Ultra5000.

Encoder output
frequency exceeds the
maximum value.

Increase the encoder

output Limit
parameter.

Decrease the encoder

interpolation
parameter.

Increase the encoder

output divider
parameter.

Reduce motor speed.

Fault Count

Displays the number of
fault encountered.

34: Ground Short
Circuit

ON indicates the motor
ground is shorted

Wiring error

Check motor power
wiring.

Motor internal ground
short

Replace motor.

Internal malfunction

Disconnect motor power
cable from drive and
enable drive with current
limit set to 0.
If fault remains, call your
A-B representative.
If fault clears, a wiring
error or an error internal
to the motor exists.

35: Soft Starting
Fault

ON indicates a soft fault
at startup.

Low AC input voltage

Check AC input voltage
on all phases.

Internal malfunction

Call your A-B
representative

36: Power
Module
Overtemperature

ON indicates an
overtemperature
condition in the power
module.

Excessive heat in power
circuitry.

Reduce acceleration

rates.

Reduce duty cycle

(ON/OFF) of
commanded motion.

Increase time

permitted for motion.

Use larger Ultra5000

and motor.

37: AC Input
Phase Loss

ON indicates incorrect
power phasing.

Loss of one or more
phases of power.

Check AC input voltage
on all phases.

Status

Description

Possible Cause

Suggested Action