Parameter Descriptions
11-9
The Main Control board software version.
Important:
Selecting option 1 or 2 also requires selection of
“Custom V/Hz,” option 2 in Torque Perf Mode (53).
Set to match the type of motor connected.
Set to the motor nameplate rated volts. The motor nameplate base
voltage defines the output voltage when operating at rated current,
rated speed, and rated temperature.
Set to the motor nameplate rated full load amps. The motor
nameplate FLA defines the output amps when operating at rated
voltage, rated speed, and rated temperature. It is used in the motor
thermal overload and in the calculation of slip.
29
Control SW Ver
Range:
0.000 to 65.256 [0.001]
Default:
Read Only
Access:
0
Path: Monitor>Drive Data
See also:
196
40
Motor Type
Range:
0 = Induction
1 = Synchr Reluc
2 = Synchr PM
Default:
0 = Induction
Access:
2
Path: Motor Control>Motor Data
See also:
41
Motor NP Volts
Range:
0.0 to Drive Rated Volts [0.1 VAC]
Default:
Based on Drive Type
Access:
1
Path: Motor Control>Motor Data
See also:
42
Motor NP FLA
Range:
0.0 to Rated Amps x 2 [0.1 Amps]
Default:
Based on Drive Type
Access:
1
Path: Motor Control>Motor Data
See also:
47, 48