Parameter Descriptions

11-9

The Main Control board software version.

Important:

Selecting option 1 or 2 also requires selection of
“Custom V/Hz,” option 2 in Torque Perf Mode (53).

Set to match the type of motor connected.

Set to the motor nameplate rated volts. The motor nameplate base
voltage defines the output voltage when operating at rated current,
rated speed, and rated temperature.

Set to the motor nameplate rated full load amps. The motor
nameplate FLA defines the output amps when operating at rated
voltage, rated speed, and rated temperature. It is used in the motor
thermal overload and in the calculation of slip.

29

Control SW Ver

Range:

0.000 to 65.256 [0.001]

Default:

Read Only

Access:

0

Path: Monitor>Drive Data

See also:

196

40

Motor Type

Range:

0 = Induction
1 = Synchr Reluc
2 = Synchr PM

Default:

0 = Induction

Access:

2

Path: Motor Control>Motor Data

See also:

41

Motor NP Volts

Range:

0.0 to Drive Rated Volts [0.1 VAC]

Default:

Based on Drive Type

Access:

1

Path: Motor Control>Motor Data

See also:

42

Motor NP FLA

Range:

0.0 to Rated Amps x 2 [0.1 Amps]

Default:

Based on Drive Type

Access:

1

Path: Motor Control>Motor Data

See also:

47, 48