Selects whether the internal or an external DB resistor option will be
used. An internal DB resistor is one that can be mounted inside the
footprint of the drive. External DB resistors are panel mounted
separately.

Proportional gain for the bus regulator. Used to adjust regulator
response.

163

DB Resistor Type

Range:

0 = Internal Res
1 = External Res
2 = None

Default:

0 = Internal Res

Access:

1

Path: Dynamic Control>Stop/Brake Modes

See also:

161, 162

!

ATTENTION: AC drives do not offer protection for
externally mounted brake resistors. A risk of fire
exists if external braking resistors are not protected.
External resistor packages must be self-protected
from overtemperature or the protective circuit shown
below, or equivalent, must be supplied.

Power On

R (L1)
S (L2)
T (L3)

Power Source

DB Resistor Thermostat

Power Off

M

M

(Input Contactor) M

Three-Phase

AC Input

AC Drive

164

Bus Reg Kp

Range:

0 to 10000

Default:

1200

Access:

2

Path: Dynamic Control>Stop/Brake Modes

See also: