Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 77

Installing Control Wiring
7-5
26
24V Power Supply
Common (internal)
n/a
Drive supplied power for logic
inputs. 150 mA maximum Load.
Digital Inputs
27
Digital In1
Stop/CF 24V AC/DC I/O Board
Opto isolated (250 V)
Low state: less than 5 V AC
High State: greater than 10 V AC
115 VAC I/O Board
4
Opto isolated (250 V)
Low state: less than 10 V AC
High State: greater than 100 V AC
361 -
366
28
Digital In2
Start
29
Digital In3
Function
Loss
30
Digital In4
Jog
31
Digital In5
Auto/
Manual
32
Digital In6
Speed
Select
1
These inputs/outputs are dependent on a number of parameters. See “Related
Parameters” column.
2
Differential Isolation - External source must be maintained at less than 160 V with
respect to PE. Input provides high common mode immunity.
3
Differential Isolation - External source must be less than 10 V with respect to PE.
4
Drive Model with 115V interface required. See figure 2.1.
Table 7.1 – Wiring Signal and Control I/O to the Terminal Block
No.
Signal
Factory
Default
Description
Re
late
d
Pa
ra
m
.
1
16
32